26.12 – PROCESS/FIRE FUNCTION
When the fire function is enabled the motor is brought to a previously defined speed and the drive ignores any alarms that
are triggered. Any disable and stop signals are still considered when the fire function is enabled.
Bypass function
If the bypass function is enabled, when an alarm is triggered during a fire condition, it is only ignored for a previously de-
fined time. After that time a digital output is activated and the alarm is enabled. The digital output is normally connected to
a power contactor that bypasses the drive and connects the motor directly to the mains.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.12.1 7840 Fire function
ENUM
Disable 0
3
RW
VS
Setting of the fire function.
0
Disable
1
Forward
2
Reverse
3
Forward bypass
Set to
0
to disable the fire function.
Set to
1
to enable the fire function. The motor turns in the normal direction of operation.
Set to
2
to enable the fire function. The motor turns in the direction opposite to the normal direction of opera-
tion.
Set to
3
to enable the fire function. The motor turns in the normal direction of operation and the bypass func-
tion is enabled.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.12.2 7842 Fire command src
LINK 16BIT
6000
0
16384
RW VS
Selection of the origin (source) of the digital signal that activates the fire function. The signal used for this
function can be set from among those available in the “
L_DIGSEL2
” selection list.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.12.3 7844 Fire speed
rpm
FLOAT
0 0 CALCI
RW
VS
Setting of the speed that must be maintained when the fire function is active.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.12.4 7846 Fire bypass delay
s
INT16
0.0 0.0 3600
RW
VS
Setting of the delay before the bypass function is activated.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.12.5 7848 Fire bypass mon
BIT
16BIT
0 0 1 R
VS
The status of the bypass function is displayed. It must be connected to the output that controls the bypass
power contactor.
Menu
PAR
Description
UM
Typo
FB BIT
Def
Min
Max
Acc
Mod
26.12.6 7850 Fire out mon
BIT
16BIT
0 0 1 R
VS
The status of the fire function is displayed. If this parameter is set to 1, the fire function is active.
Содержание ADV200 WA
Страница 84: ...84 ADV200 WA Functions description and parameters list 22 3 FUNCTIONS DC BRAKING ...
Страница 274: ...274 ADV200 WA Block Diagrams G Block Diagrams System Diagrams Index Drive overview ...
Страница 275: ...ADV200 WA Block Diagrams 275 References ...
Страница 276: ...276 ADV200 WA Block Diagrams Ramps Multireference ...
Страница 277: ...ADV200 WA Block Diagrams 277 Motorpotentiometer Jog function ...
Страница 278: ...278 ADV200 WA Block Diagrams Monitor function ...
Страница 279: ...ADV200 WA Block Diagrams 279 ...
Страница 280: ...280 ADV200 WA Block Diagrams Commands ...
Страница 281: ...ADV200 WA Block Diagrams 281 ...
Страница 282: ...282 ADV200 WA Block Diagrams Digital inputs ...
Страница 283: ...ADV200 WA Block Diagrams 283 Digital outputs ...
Страница 284: ...284 ADV200 WA Block Diagrams Analog inputs ...
Страница 285: ...ADV200 WA Block Diagrams 285 ...
Страница 286: ...286 ADV200 WA Block Diagrams Analog outputs ...
Страница 287: ...ADV200 WA Block Diagrams 287 Speed reg gains ...
Страница 288: ...288 ADV200 WA Block Diagrams VF parameters ...
Страница 289: ...ADV200 WA Block Diagrams 289 Functions ...
Страница 290: ...290 ADV200 WA Block Diagrams ...
Страница 291: ...ADV200 WA Block Diagrams 291 ...
Страница 292: ...292 ADV200 WA Block Diagrams ...
Страница 293: ...ADV200 WA Block Diagrams 293 Process ...
Страница 294: ...294 ADV200 WA Block Diagrams ...
Страница 295: ...ADV200 WA Block Diagrams 295 ...
Страница 296: ...296 ADV200 WA Block Diagrams ...
Страница 297: ...ADV200 WA Block Diagrams 297 ...
Страница 298: ...298 ADV200 WA Block Diagrams ...
Страница 299: ......