132
ADV200
WA • Functions description and parameters list
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.68 7820 Analog 2 err act
ENUM
Ignore
0
4
RW VS
Setting of the behaviour of the drive if the measurement error alarm is present on analog channel 2. If an
analog measurement is out of the allowed range an
Analog x err
alarm is generated. This control is only pos-
sible for 4-20 mA, PT100, PT1000, NI1000 probes. For temperature probes both short-circuits and power loss
on the cable are detected.
For the 4-20 mA only power loss on the cable is detected.
0
Ignore
1
Warning
2
Disable
3
Stop
4
Fast stop
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.69 7822 Analog 2 err delay
s
FLOAT
1
0.1
60
RW VS
Setting of the delay after which the alarm is activated.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.70 7824 Analog 1x err act
s
ENUM
Ignore
0
4
RW VS
Setting of the behaviour of the drive if the measurement error alarm is present on analog channel 1 of the
expansion card. If an analog measurement is out of the allowed range an
Analog x err
alarm is generated.
This control is only possible for 4-20 mA, PT100, PT1000, NI1000 probes. For temperature probes both short-
circuits and power loss on the cable are detected.
For the 4-20 mA only power loss on the cable is detected.
0
Ignore
1
Warning
2
Disable
3
Stop
4
Fast stop
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.71 7826 Analog 1x err delay
s
UINT16
1
0.1
60
RW VS
Setting of the delay after which the alarm is activated.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.72 7828 Analog 2x err act
ENUM
Ignore
0
4
RW VS
Setting of the behaviour of the drive if the measurement error alarm is present on analog channel 2 of the
expansion card. If an analog measurement is out of the allowed range an
Analog x err
alarm is generated.
This control is only possible for 4-20 mA, PT100, PT1000, NI1000 probes. For temperature probes both short-
circuits and power loss on the cable are detected.
For the 4-20 mA only power loss on the cable is detected.
0
Ignore
1
Warning
2
Disable
3
Stop
4
Fast stop
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.73 7830 Analog 2x err delay
s
UINT16
1
0.1
60
RW VS
Setting of the delay after which the alarm is activated.
Содержание ADV200 WA
Страница 84: ...84 ADV200 WA Functions description and parameters list 22 3 FUNCTIONS DC BRAKING ...
Страница 274: ...274 ADV200 WA Block Diagrams G Block Diagrams System Diagrams Index Drive overview ...
Страница 275: ...ADV200 WA Block Diagrams 275 References ...
Страница 276: ...276 ADV200 WA Block Diagrams Ramps Multireference ...
Страница 277: ...ADV200 WA Block Diagrams 277 Motorpotentiometer Jog function ...
Страница 278: ...278 ADV200 WA Block Diagrams Monitor function ...
Страница 279: ...ADV200 WA Block Diagrams 279 ...
Страница 280: ...280 ADV200 WA Block Diagrams Commands ...
Страница 281: ...ADV200 WA Block Diagrams 281 ...
Страница 282: ...282 ADV200 WA Block Diagrams Digital inputs ...
Страница 283: ...ADV200 WA Block Diagrams 283 Digital outputs ...
Страница 284: ...284 ADV200 WA Block Diagrams Analog inputs ...
Страница 285: ...ADV200 WA Block Diagrams 285 ...
Страница 286: ...286 ADV200 WA Block Diagrams Analog outputs ...
Страница 287: ...ADV200 WA Block Diagrams 287 Speed reg gains ...
Страница 288: ...288 ADV200 WA Block Diagrams VF parameters ...
Страница 289: ...ADV200 WA Block Diagrams 289 Functions ...
Страница 290: ...290 ADV200 WA Block Diagrams ...
Страница 291: ...ADV200 WA Block Diagrams 291 ...
Страница 292: ...292 ADV200 WA Block Diagrams ...
Страница 293: ...ADV200 WA Block Diagrams 293 Process ...
Страница 294: ...294 ADV200 WA Block Diagrams ...
Страница 295: ...ADV200 WA Block Diagrams 295 ...
Страница 296: ...296 ADV200 WA Block Diagrams ...
Страница 297: ...ADV200 WA Block Diagrams 297 ...
Страница 298: ...298 ADV200 WA Block Diagrams ...
Страница 299: ......