128
ADV200
WA • Functions description and parameters list
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.40
4660 PhLoss activity
ENUM
Disable
0
4
ERW VS
Setting of the behaviour of the drive in case of a no phase alarm. This alarm indicates the absence of a drive
power supply phase.
0
Ignore
1
Warning
2
Disable
3
Stop
4
Fast stop
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.41
4662 PhLoss restart
ENUM
Disable
0
1
ERW VS
Enabling of automatic restart after the no phase alarm.
0 Disable
1 Enable
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.42
4664 PhLoss restart time
ms
UINT16
1000
120
10000
ERW VS
Setting of the time within which the
Phase loss
alarm must be reset in order to perform automatic restart.
(Time with alarm signal 100 msec).
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.43
4670 Optionbus activity
ENUM
Disable
0
4
ERW VS
Setting of the behaviour of the drive in case of an
Opt Bus Fault
alarm.
0
Ignore
1
Warning
2
Disable
3
Stop
4
Fast stop
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.44
4672 Optbus fault en src
LINK 16BIT
6002
0
16384
ERW VS
Selection of the origin (source) of the signal to be used as “
Opt bus fault
” [17] alarm. The terminal that can
be used for this function can be selected from among those listed in the “
L_DIGSEL1
” selection list.
The default is PAR 6002
One
. If it is selected the PAR 1030
Local / remote mon
, it can inhibit the alarm only
when you switch from “
Remote
” to “
Local
”.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.45
4680 Ground Fault thr
perc FLOAT
10.0
0
150.0
ERWS VS
Setting of the threshold for the ground short circuit alarm
Ground Fault.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
24.46
4700 Alarm dig sel 1
ENUM
No alarm
0
40
ERW VS
24.47
4702 Alarm dig sel 2
ENUM
No alarm
0
40
ERW VS
24.48
4704 Alarm dig sel 3
ENUM
No alarm
0
40
ERW VS
24.49
4706 Alarm dig sel 4
ENUM
No alarm
0
40
ERW VS
Setting of the alarm signal to enable on a digital output. The digital output is selected using parameters
Alm
dig out mon 1÷4
, which can be enabled in the
L_DIGSEL1
selection list.
0
No alarm
1
Overvoltage
Содержание ADV200 WA
Страница 84: ...84 ADV200 WA Functions description and parameters list 22 3 FUNCTIONS DC BRAKING ...
Страница 274: ...274 ADV200 WA Block Diagrams G Block Diagrams System Diagrams Index Drive overview ...
Страница 275: ...ADV200 WA Block Diagrams 275 References ...
Страница 276: ...276 ADV200 WA Block Diagrams Ramps Multireference ...
Страница 277: ...ADV200 WA Block Diagrams 277 Motorpotentiometer Jog function ...
Страница 278: ...278 ADV200 WA Block Diagrams Monitor function ...
Страница 279: ...ADV200 WA Block Diagrams 279 ...
Страница 280: ...280 ADV200 WA Block Diagrams Commands ...
Страница 281: ...ADV200 WA Block Diagrams 281 ...
Страница 282: ...282 ADV200 WA Block Diagrams Digital inputs ...
Страница 283: ...ADV200 WA Block Diagrams 283 Digital outputs ...
Страница 284: ...284 ADV200 WA Block Diagrams Analog inputs ...
Страница 285: ...ADV200 WA Block Diagrams 285 ...
Страница 286: ...286 ADV200 WA Block Diagrams Analog outputs ...
Страница 287: ...ADV200 WA Block Diagrams 287 Speed reg gains ...
Страница 288: ...288 ADV200 WA Block Diagrams VF parameters ...
Страница 289: ...ADV200 WA Block Diagrams 289 Functions ...
Страница 290: ...290 ADV200 WA Block Diagrams ...
Страница 291: ...ADV200 WA Block Diagrams 291 ...
Страница 292: ...292 ADV200 WA Block Diagrams ...
Страница 293: ...ADV200 WA Block Diagrams 293 Process ...
Страница 294: ...294 ADV200 WA Block Diagrams ...
Страница 295: ...ADV200 WA Block Diagrams 295 ...
Страница 296: ...296 ADV200 WA Block Diagrams ...
Страница 297: ...ADV200 WA Block Diagrams 297 ...
Страница 298: ...298 ADV200 WA Block Diagrams ...
Страница 299: ......