ADV200 WA • Functions description and parameters list
101
If the signal is not enabled it means the power supply is not present (
Mains voltage not OK
), whereas if the
signal is enabled it means the power supply is present (
Mains voltage OK
).
In the default condition the origin of the
Powerloss mains src
signal is
Zero
.
The user must connect an external sensor to inform the drive of the mains supply status.
If the function is configured as
Powerloss mode = Restart
, when the
Mains voltage OK
signal is enabled
the drive stops the deceleration ramp and passes to the set reference.
For machines with several drives the external sensor signal must only be connected to the master drive.
22.8 – FUNCTIONS/COMPARE
This function allows the comparison among two signals or values.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
22.8.1 3650 Dig compare input 1
perc FLOAT 32
0.0
-100.0
100.0
ERW VS
Setting of the digital value of the first element of comparison.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
22.8.2 3652 Dig compare input 2
perc FLOAT 32
0.0
-100.0
100.0
ERW VS
Setting of the digital value of the second element of comparison.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
22.8.3 3660 Compare input 1 src
LINK 32
3650
0
16384
ERW VS
Selection of the origin (source) of the signal to be used as the first term of comparison. The values that can be
selected in the compare function are listed in the “
L_CMP
” selection list.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
22.8.4 3662 Compare input 2 src
LINK 32
3652
0
16384
ERW VS
Selection of the origin (source) of the signal to be used as the second term of comparison. The values that
can be selected in the compare function are listed in the “
L_CMP
” selection list.
Menu
PAR
Description
UM
Type
FB BIT
Def
Min
Max
Acc
Mod
22.8.5 3670 Compare function
ENUM
None
0
8
ERW VS
Setting of the compare function between
Compare input 2
and
Compare input 1
to enable
Cmp output
.
0
None
Содержание ADV200 WA
Страница 84: ...84 ADV200 WA Functions description and parameters list 22 3 FUNCTIONS DC BRAKING ...
Страница 274: ...274 ADV200 WA Block Diagrams G Block Diagrams System Diagrams Index Drive overview ...
Страница 275: ...ADV200 WA Block Diagrams 275 References ...
Страница 276: ...276 ADV200 WA Block Diagrams Ramps Multireference ...
Страница 277: ...ADV200 WA Block Diagrams 277 Motorpotentiometer Jog function ...
Страница 278: ...278 ADV200 WA Block Diagrams Monitor function ...
Страница 279: ...ADV200 WA Block Diagrams 279 ...
Страница 280: ...280 ADV200 WA Block Diagrams Commands ...
Страница 281: ...ADV200 WA Block Diagrams 281 ...
Страница 282: ...282 ADV200 WA Block Diagrams Digital inputs ...
Страница 283: ...ADV200 WA Block Diagrams 283 Digital outputs ...
Страница 284: ...284 ADV200 WA Block Diagrams Analog inputs ...
Страница 285: ...ADV200 WA Block Diagrams 285 ...
Страница 286: ...286 ADV200 WA Block Diagrams Analog outputs ...
Страница 287: ...ADV200 WA Block Diagrams 287 Speed reg gains ...
Страница 288: ...288 ADV200 WA Block Diagrams VF parameters ...
Страница 289: ...ADV200 WA Block Diagrams 289 Functions ...
Страница 290: ...290 ADV200 WA Block Diagrams ...
Страница 291: ...ADV200 WA Block Diagrams 291 ...
Страница 292: ...292 ADV200 WA Block Diagrams ...
Страница 293: ...ADV200 WA Block Diagrams 293 Process ...
Страница 294: ...294 ADV200 WA Block Diagrams ...
Страница 295: ...ADV200 WA Block Diagrams 295 ...
Страница 296: ...296 ADV200 WA Block Diagrams ...
Страница 297: ...ADV200 WA Block Diagrams 297 ...
Страница 298: ...298 ADV200 WA Block Diagrams ...
Страница 299: ......