9.7 Voltage level of the inverter for safe operations
The minimum time
between the moment in which an ADV200
SP
drive is disabled from the mains and that in
which an operator can operate on internal parts of the drive, without the danger of electric shock
, is 5 minutes.
The value consider the time to turn-off for a drive supplied at 460Vac
+10%, without any options (time indicated
for disabled drive condition).
9.8 Cooling
All the Drives have internal fans.
Sizes
Dissipated power
Dissipated power
(ADV200 SP-EH
models)
Airflow of fan
(W)
(W)
Heatsink (m
3
/h)
Internal (m
3
/h)
1015
60
-
32
26
1022
90
-
32
32
1030
100
-
32
32
1040
120
-
32
32
1055
160
-
32
32
2075
200
-
32
32
2110
250
107,5
56 x 2
32
2150
300
118
56 x 2
32
3185
380
130
80 x 2
32
3220
460
-
80 x 2
32
3300
600
151
80 x 2
32
4370
900
218
2 x 250
2 x 50
4450
1000
235
2 x 250
2 x 50
4550
1290
255
2 x 250
2 x 50
5750
1760
293
2 x 285
1 x 170
5900
2150
430
2 x 355
2 x 170
51100
2400
520
2 x 355
2 x 170
61320
2850
-
3 x 310
2 x 170
61600
3600
-
3 x 310
2 x 170
9.9 Weight and dimensions
Sizes
ADV200 SP-...-4
ADV200 SP-EH-...-4
Weight (kg) Weight (lbs)
Sizes
ADV200 SP-...-4-DC
Weight (kg) Weight (lbs)
1015 ... 1055
5,8
12,8
-
-
-
2075 ... 2150
10,2
22,5
-
-
-
3185 ... 3220
16,4
36,2
3220
12
26,5
3300
22
48,5
3300
18
39,7
4370 ... 4550
32
70,6
4370 ... 4550
24
52,9
5750 ... 51100
60
132
5750 ... 51100
40
88,2
61320 ... 61600
90
198
61320 ... 61600
68
150
Note !
Weights referred to standard drive with keypad, without options, packaging not included.