52
4. CONFIGURATION
80703B_MHW_2850T/3850T_02-2019_ENG
4.13.3. Configuring the program
Configuring a program consists in defining all the param-
eters, functions, times, interactions with other programs
and commands that characterise it and make it suitable for
performing the task for which it is designed.
To configure an existing program, just select it from
the PROGRAMS menu list, and then touch the button
to access the configuration pages.
The configuration procedure is developed through 4 sec-
tions (Base, Segments, GETlogic, Reports), each consisting
of one or more configuration pages. Each page contains the
name of the program.
If any changes have been made, the
Save
and
Cancel
buttons appear on the pages in order to save the changes
or cancel them. Touching these buttons also closes the
configuration procedure.
4.13.3.1. Base program configuration
This is the
page (1)
that appears when activating the pro-
gram configuration procedure.
To navigate to other pages in the Base section, just touch
the corresponding number or select the page from the
drop-down menu that appears by touching the "Base" label
or by using keyboard keys
and
.
BASE - page 1
Parameter
Description
Possible values
Program name
Program name.
Touching the field opens a pop-up window with
which you can select another program.
Alphanumeric string, max. 16 characters long.
The name must be unique (duplicates are not
allowed).
Characters allowed a ... z, A ... Z, 0 ... 9, _.
Number
Absolute program identification number
Automatic value.
Description
Extended program description. It is used to iden-
tify the program running on different pages.
Alphanumeric text. The maximum length of the
text is 23 (model 2850T) or 30 (model 3850T)
characters.
Time unit
It is the time base shared by all program seg-
ments. The active base is highlighted in green. To
change, touch the time base you want to use.
m : s
= Minutes : Seconds
h : m
= Hours : Minutes
d : h
= Days : Hours
N° repetitions
Number of automatic program repetitions before
it stops.
0 means the program runs one time and then
stops; 1 means the program is run twice and
then stops, and so on. A program can be run
automatically up to 10,000 times.
0
...
9999
Start Mode
Select the reference value at program start (SP =
PV or SP can be set).
Start from SP
Start from PV
Stop mode
Operating mode at the end of the program in
END status.
DO off
:
Last step
Reset
Ready mode
Behaviour of outputs when the program switches
from any state to READY.
Unchanged Out
DO off
Out = PV
Unchanged Out, DO off
Out = PV, DO off, PID disabled
Start state
Status when the controller is switched on.
The Run, Hold, and End modes are only active
if the program was running (Run or Hold) when
turned off, otherwise the program is always
brought to the Ready state.
Ready
Run
Hold
End
NOTE 1 : Enable the PIDs associated with a profile when the profile starts, using the number in the PID column in the pro-
grammer’s BASE2 page as reference for association.
NOTE 2: If the PID operates a valve, it will not be possible to disable it at the end of the programme
NOTE 3 : Before it can start again, the PID must operate empty to reset the integral
Содержание 2850T
Страница 2: ......
Страница 6: ...80703B_MHW_2850T 3850T_02 2019_ENG 4...
Страница 10: ...80703B_MHW_2850T 3850T_02 2019_ENG 8...
Страница 20: ...80703B_MHW_2850T 3850T_02 2019_ENG 18...
Страница 34: ...80703B_MHW_2850T 3850T_02 2019_ENG 32...
Страница 104: ...80703B_MHW_2850T 3850T_02 2019_ENG 102...
Страница 106: ...80703B_MHW_2850T 3850T_02 2019_ENG 104...
Страница 124: ...80703B_MHW_2850T 3850T_02 2019_ENG 122...
Страница 128: ...80703B_MHW_2850T 3850T_02 2019_ENG 126...
Страница 156: ...80703B_MHW_2850T 3850T_02 2019_ENG 154...
Страница 162: ...80703B_MHW_2850T 3850T_02 2019_ENG 160...