7.7. Practical configuration examples
7.7.1. Loop configuration
The example describes the procedure for configuring a PID
with the following features:
•
Heat/Cool action;
•
K thermocouple input;
•
digital control output with Heat/Cool action;
•
2 absolute Maximum and Minimum alarms.
For the configuration of the PID, the following variables
(signals) of the F-MIX module are used:
Type
Name
Description
Analog input (AI1)
AI_01
Input signal 1
Digital Output
(DO1)
DO_01
Digital output 1 -
Heat action
Digital Output
(DO2)
DO_02
Digital output 2 -
Cool action
Digital Output
(DO3)
DO_03
Digital output 3 -
HIGH alarm
Digital Output
(DO4)
DO_04
Digital output 4 -
LOW alarm
To configure the PID loop, proceed as follows:
1. Login with level 2 password.
2. Select
SETUP
.
3. Select
HW CFG
.
4. Select module
F_MIX
.
5. Configure the type of thermocouple associated with
channel 1 (AI1) of the F-MIX module.
Touch
IN1 Type
and select
TC_K
(K thermocouple).
The default variable associated with the temperature
value of channel 1 is AI_01.
Содержание 2850T
Страница 2: ......
Страница 6: ...80703B_MHW_2850T 3850T_02 2019_ENG 4...
Страница 10: ...80703B_MHW_2850T 3850T_02 2019_ENG 8...
Страница 20: ...80703B_MHW_2850T 3850T_02 2019_ENG 18...
Страница 34: ...80703B_MHW_2850T 3850T_02 2019_ENG 32...
Страница 104: ...80703B_MHW_2850T 3850T_02 2019_ENG 102...
Страница 106: ...80703B_MHW_2850T 3850T_02 2019_ENG 104...
Страница 124: ...80703B_MHW_2850T 3850T_02 2019_ENG 122...
Страница 128: ...80703B_MHW_2850T 3850T_02 2019_ENG 126...
Страница 156: ...80703B_MHW_2850T 3850T_02 2019_ENG 154...
Страница 162: ...80703B_MHW_2850T 3850T_02 2019_ENG 160...