FUNCTION
FUNCTION / DC braking
The Function allows to stop the motor with a direct current braking.
The current injection can be activated via an external command, via the
I00.00 - DCbrake
cmd src
source or automatically via an internal command when the stop command is
performed.
Such command can be activated by setting
I00.10 - DCbrake mode
= At stop.
It is possible to have simultaneously both the internal and the external command.
They both work on a OR logic. Furthermore, the function is made of:
-
a waiting phase between the command emission and the duration of the
programmable injection
-
a direct current injection phase, whose intensity and duration can be programmed
Via
I00.11 - DCbrake delay
it is possible to set the waiting phase between the command
and the injection duration.
N
OTE
!
If the external command is a pulse shorter than the programmed injection time, the
injection phase lasts for the programmed time.
If the external command is a pulse longer than the programmed injection time, the
injection phase lasts till the end of the external command.
With
I00.20 -DCBrake duration
it is possible to set the current injection duration while
I00.21 -DCBrake current
allows to set the current intensity.
Содержание ARTDrive Vector V2 400Vac Series
Страница 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Страница 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Страница 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Страница 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Страница 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Страница 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...