MENU
[Unit] Access Default
Min/Max
Format Reg.Mode Level Ipa
Parameter Name
Description
Chapter 6 Parameter • 130
ARTDrive V2 series - Instruction Manual
ª
ª
ª
ª
ª
Pick List 3
C00.09 Stop src
N/A
RWS
(*)
Plist 03
PIN
V-F-S-B
Easy 8085
(*) Ipa 4001 - ONE = Default (Europe)
Ipa 4023 - DI 3 = Default (American)
It allows to select the signal Stop command of 3-wires; see
C00.25 - FRC cmd mode
description below.
ª
ª
ª
ª
ª
Pick List 3
C00.20 Commands select
N/A
RWS
2
0/4
DV
V-F-S-B
Easy 4002
[0] TerminalLevel
The drive is controlled via terminal strip using Level sensitive signals
[1] TerminalEdge
The drive is controlled via terminal strip using Edge sensitive signals
[2] DigitalLevel
The drive is controlled from a communication or application card using level
sensitive signals
[3] DigitalEdge
The drive is controlled from a communication or application card using edge
sensitive signals
[4] I O keys
The drive is controlled from the keyboard using the I O keys; terminal 12
(Enable) to 24Vdc are required
Setting of this parameter is not allowed while terminal enable is active.
C00.21 En/Disable mode
N/A
RWS
0
0/3
DP
V-F-S-B
Easy 4004
[0] Off
Not active
[1] Stop/FS&Spd=0
Stop / Fast stop & Speed equal to zero
[2] Stop&Spd=0
Stop & Speed equal to zero
[3] FS&Spd=0
Fast stop & Speed equal to zero
It controls the action time of the stop condition.The drive can act:
-
With the enable and start/stop commands controlled independently by the
operator (
C00.21
=[0])
-
With just the start/stop command, while the enable and disable command is
controlled by the drive. In this case with the start command the drive enables itself.
When the stop command is generated (and/or fast stop according to the
C00.21 - En/Disable mode
selection), the Drive reaches a zero speed and after a
C00.22 - Spd 0 dis dly
, it disables itself automatically.
N
OTE
!
Setting of this parameter is not allowed while terminal enable is active.
C00.22 Spd 0 dis dly
[ms]
RWS
1000
16/10000
PP
V-F-S-B
Easy 4006
Delay time between the zero speed and the disabling procedure
Содержание ARTDrive Vector V2 400Vac Series
Страница 1: ...Instruction Manual ARTDrive ARTDrive Vector AC Drives V2 series 400Vac Class 575Vac Class...
Страница 14: ...0 14 Chapter 0 Safety Precautions ARTDrive V2 series Instruction manual...
Страница 40: ...40 Chapter 3 Installation Guidelines ARTDrive V2 series Instruction Manual...
Страница 92: ...92 Chapter 5 Quick Start Up Guide ARTDrive V2 series Instruction Manual...
Страница 358: ...358 Chapter 8 Appendix ARTDrive V2 series Instruction Manual...
Страница 376: ...Chapter 9 Pick Lists 376 ARTDrive V2 series Instruction manual...