Gas Regulator with SSV:

RG = Attacchi filettati

RGD=Attacchi flangiati

DIMENSIONI:

032= 1" 1/4

040= 1" 1/2

050= 2”

SSV:

Slam Shut Valve

PRESSIONE di 

MASSIMA:

 _  = 500mbar

5B = bar

Depending on which model, GAS REGULATOR SSV are marked by laser with 

their technical characteristics. (Fig.1):

MARKING

 Fig.1

Pe max: 5bar 

        Body:     1"1/4

Pd: 60 

I

130bar 

        Upso: 30-60mbar 

T. amb.: -20 

 

+60°C         Opso: 150-250mbar

Group:   2

 

           

S/N 188801

   

 

RG032-5B-SSV

Any maintenance operation must be performed by qualified personnel. 

This device must be installed in accordance with the laws in force.

The GAS REGULATOR SSV is normally installed before the user. It can be installed 

in a horizontal position and it must be installed with the arrow on the body towards 

the user. (Fig.2).

N.B. Install the GAS REGULATOR SSV away from atmospheric agents.

INSTALLATION AND POSITIONING

4

GENERAL DESCRIPTION

GAS REGULATOR with SSV

Impulse

socket

Distance: 

Impulse socket /

Gas regulator SSV

Copper Tube

Cod.

5bar

SPY2-15

SPN2-15

SPR2-15

SPBK2-15

SPG2-15

SPBR2-15

Color

YELLOW

NEUTRAL

RED

BLACK

GREEN

BROWN

RANGE SPRING (mbar) 

Range (mbar)

I

22

10 

I

27

28 

I

70

60 

I

130

120 

I

300

220 

I

480

Gas Regulator

with Slam Shut Valve integrated 

for Over (OPSO) and Under (UPSO) pressure 500mbar/5bar

Mod.

 RG & RGD

Cod.

SPY2-U

SPN2-U

Color

YELLOW

NEUTRAL

Range (mbar)

I

14

30 

60

Cod.

SPB2-O

SPG2-O

SPBR2-O

Color

BLACK

GREEN

BROWN

Range (mbar)

150 

I

250

300 

I

500

500 

I

700

UPSO SPRING (mbar)

OPSO SPRING (mbar)

GAS REGULATOR SSV are single-stage gas regulators with pressure blocking 

device.

GAS REGULATOR SSV can be installed in systems with automatic gas burners 

and in industrial gas distribution systems.

GAS REGULATOR SSV have three diaphragms fitted inside them: a operating 
diaphragm 

9

,  a  compensation  diaphragm 

13

  and  a  safety  diaphragm 

16

 

(refer to Fig. 3).

A  breather  pipe  and  external  discharge  is  not  necessary  because  the  safety 

membrane avoids more than 30 dm3 / h, point 3.3.2 of the UNI-EN88-1: 2011 

Norms.

The GAS REGULATOR SSV comply with the ATEX Directive 2014/34 / EU as 

device of group II, category 2G and as device of group II, category 2D; for this 

reason it is suitable for installation in zones 1 and 21 (as well as in zones 2 and 

22) as classified in Annex I to Directive 99/92 / EC.

They are NOT suitable for installation in zones 0 and 20 as defined in the  Direc-

tive 99/92 / EC.

We  recommend  checking  the  CEI  EN  60079-10-1  standard  to  determine  the 

qualification and extension of hazardous areas.

GAS REGULATOR SSV are equipped with:

•  OVER  PRESSURE  blocking  device  (SSV)  that  blocks  the  pressure  flow 

when the output pressure of the GAS REGULATOR SSV exceeds the set limit 

(OPSO).

•  UNDER  PRESSURE  blocking  device  that  blocks  the  pressure  flow  when 

the output pressure of the GAS REGULATOR SSV is lower than the set limit 

(UPSO).

WARNING: The GAS REGULATOR SSV will remain operated only if the pres-

sure  downstream  is  between  the  maximum  value  (OPSO)  and  the  minimum 

value (UPSO) set.

Fig.3

Fig.2

• Before proceeding with the installation, make sure that the gas supply has been 

shut-off.

• Check that the line pressure does NOT EXCEED the maximum pressure stated 

on the LABEL OF REGULATOR SSV.

• Make sure to respect the gas flow indicated by the arrow on the body of the 

GAS REGULATOR SSV which must always be directed towards the user.

• It is necessary to install an 

impulse socket

 for the shut-off valve with G 1/8 

“connection and an 

impulse socket

 at the output of the GAS REGULATOR SSV 

at a distance of 5 times the nominal diameter of the pipe from the output of the 

same (Fig.3).

The two impulse sockets must be connected to each other with a copper tube 

with G 1/8 “connection.

GAS REGULATOR SSV if installed according all the indications of the following 

document it will not constitute a source of danger.

Only in particular fault conditions it will they be able to release flammable sub-

stances into the environment.

If the GAS REGULATOR SSV  are installed in critical area (places not protected, 

lack of servicing, lacking availability of ventilation) and, especially in presence, 

close to the regulator, of potential sources of primer and/or dangerous devices 

during the normal working because susceptible to origine electric arcs or sparks, 

it is necessary to value before the compatibility between the regulator and these 

devices, we recommend removing the protective cap and connecting a tube with 

M10X1 connection. Place the other end of the tube outside the room. In this case 

the exhaust  gas will be expelled into the external environment.

Make sure that  debris or scraps have been created inside the network piping.

Carefully check the connections made and check the tightness of the system. 

GAS 

REGULATOR

Slam Shut Valve

GAS REGULATOR 500mbar/5 bar

SLAM SHUT VALVE

Cod.

500mbar

SPY2-5

SPN2-5

SPR2-5

SPBK2-5

SPG2-5

SPBR2-5