6.5.1
Air Requirement
FRS valve size: Process
housing / CIP housing
Actuator Ø
[mm]
Air requirement
(dm
3
n
/Stroke)
dm
3
n
at 1.01325 bar
at 0 °C as per DIN
1343
DN50/DN65
142
0.22
DN50/DN80
142
0.22
DN80/DN100
169
0.79
3"OD/DN100
169
0.79
DN100/DN125
169
0.79
4"OD/DN125
169
0.79
DN125/DN150
204
1.57
DN350/DN125
169
0.79
6.5.2
Establishing Hose Connections
To ensure reliable operation, the compressed air hoses must be cut exactly
square.
Tools required:
•
A hose cutter
Carry out the following steps:
1.
Shut off the compressed air supply.
2.
Use the hose cutter to cut the pneumatic hoses square.
3.
Push the air hose into the air connector of the drive.
4.
Re-open the compressed air supply.
®
Establish a hose connection.
6.6
Electrical connections
Danger
Live parts
Electrical shock can result in serious personal injury or death.
► Only allow properly qualified staff to carry out work on the electrical
equipment.
► Prior to establishing electrical connections check the maximum
permissible operating voltage.
Assembly and installation
Electrical connections
430BAL013059EN_7
24.03.2022
29