2.
Connect the solenoid valve (solenoid valve) Y1, Y2 and Y3 to the terminal
strip of the sensor module (43) according to the existing number of solenoid
valves.
®
The sensors and solenoid valves are connected.
®
Done
10.5
Maintenance
10.5.1 Replacing the Seals on the Base
Only use sound absorber (21, 26) or exhaust air throttle (21.1) types specified in
chapter “Technical data” . Do not grease these spare parts before fitting them.
Fig.55
Caution!
► On VARIVENT actuators with a vent hole in the actuator cover the
control top may only be fitted without O-ring (54)!
10.5.2 Maintenance of Sound Absorber, Filter, Non-Return Valve and Throttles
Carry out the following steps:
1.
Take out the O-rings (31, 53, 54) and replace them with new ones.
Servicing
Maintenance
430BAL013985EN_6
100
25.04.2023