Assembly
3
|
Areas of application
4.1 Setting up
INFO
New compressors are factory-filled with inert gas (3 bar nitrogen).
Leave this service charge in the compressor for as long as pos-
sible and prevent the ingress of air.
Immediately after connecting the Plusbox to the refrigeration
system, close the shut-off valves in the suction, discharge lines
etc. and evacuate the compressor.
Check the condensingn unit for transport damage before starting
any work.
-
-
-
3.1 Areas of application
•
The operating limits of the condensing units differ to the respective compressor.
The really operating limits can be found on the Internet on our software (VAP) under
vap.gea.com.
Do not lift manually
Use lifting gear
Transport preferably via forklift truck,
alternatively bolted to a pallet
Provide adequate clearance for maintenance work
.
Distance from wall to condenser minimum 300 mm.
Do not use in a dusty, damp atmosphere or a combustible
environment.