4.
Refrigerant Sensor High High Warning Enabled
This parameter is used to select whether the sensor is configured to annunciate a high high refrigerant warn-
ing condition. The options are:
•
Enabled
•
Disabled
5.
Refrigerant Sensor High High Warning
This parameter is used to select the refrigerant level above which a high high refrigerant warning condition
will be triggered. It will only appear if the
Refrigerant Sensor High High Warning
parameter is set to
Enabled
.
The value is measured in parts per million.
Hint!
The minimum and maximum values of this parameter vary based on the values of the High
Warning and High High Shutdown parameters. The minimum vale of this parameter will be
equal to the current value of the high warning parameter, and the maximum value will be equal
to the current value of the high high shutdown parameter.
6.
Refrigerant Sensor High High Warning Delay
This parameter is used to select the period of time for which a high high refrigerant warning condition must
persist before an annunciation will be triggered. It will only appear if the
Refrigerant Sensor High High Warn-
ing
parameter is set to
Enabled
. The value is measured in seconds.
7.
Refrigerant Sensor High High Shutdown Enabled
This parameter is used to select whether the sensor is configured to annunciate a high high refrigerant shut-
down condition. The options are:
•
Enabled
•
Disabled
8.
Refrigerant Sensor High High Shutdown
This parameter is used to select the refrigerant level above which a high high refrigerant shutdown condition
will be triggered. It will only appear if the
Refrigerant Sensor High High Shutdown
parameter is set to
Ena-
bled
. The value is measured in parts per million.
9.
Refrigerant Sensor High High Shutdown Delay
This parameter is used to select the period of time for which a high high refrigerant shutdown condition must
persist before an annunciation will be triggered. It will only appear if the
Refrigerant Sensor High High Shut-
down
parameter is set to
Enabled
. The value is measured in seconds.
3.7
Compressor Operating Data
Operating Data is displayed on the main Omni
Compressor
screen detailed in Section 2.5.1, Page 31. Below is a
list of standard operating variables and a brief description of their functions.
Control
Compressor Operating Data
Instruction Manual | GEA Omni™
Control panel
176
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
Содержание Omni
Страница 1: ...Control panel GEA Omni Instruction Manual E_806550_2 ...
Страница 238: ......