1.
Compressor Service Notification
This parameter is used to select whether the panel will annunciate notifications when service tasks are due.
The options are:
•
Enabled
•
Disabled
3.2
Oil Still Control Parameters
Control parameters are displayed on the main compressor screen detailed in Section 2.5.1, Page 31. Below is a
list of all control parameters and a brief description of their function.
3.2.1
Oil Still
Parameter
Units
Minimum
Maximum
Default
Oil Return Transfer Mode
Selection – See Description
Oil Return Automatic Transfer Day
Selection – See Description
Oil Return Automatic Transfer Hour
Hours
0 h
24 h
12 h
Oil Return Automatic Transfer
Minute
Minute
0 min
60 min
0 min
Hot Gas Return Cycle Timer
Seconds
0 s
3600 s
30 s
Heater On Temperature
°C
10 °C
70 °C
20 °C
°F
50 °F
158 °F
68 °F
Heater Off Temperature
°C
10 °C
70 °C
70 °C
°F
50 °F
158 °F
158 °F
Oil Drain
Seconds
5 s
3600 s
30 s
Drain Delay
Seconds
5 s
21600 s
70 s
Oil Return
Seconds
5 s
3600 s
20 s
Return Delay
Seconds
5 s
21600 s
80 s
Instruction Manual | GEA Omni™
Control panel
Control
Oil Still Control Parameters
GEA Refrigeration North America, Inc. | E_806550_2 | Generated 12.01.2016
155
Содержание Omni
Страница 1: ...Control panel GEA Omni Instruction Manual E_806550_2 ...
Страница 238: ......