22
D
GB
F
E
96422-07.2018-DGbFEI
HGX34e/ ...
145-4 S CO
2
170-4 S CO
2
210-4 S CO
2
255-4 S CO
2
Designation
Item No.
Item No.
Item No.
Item No.
Set of gaskets
81580
Valve plate kit
81270
81269
Set piston/connecting rod
81073
81074
81075
81076
Set connecting rod
81268
Only use genuine GEA spare parts!
7.3 Spare part recommendation
HGX22e/ ...
85-4 S CO
2
105-4 S CO
2
130-4 CO
2
Designation
Item No.
Item No.
Item No.
Set of gaskets
81579
Valve plate kit
81270
81269
Set piston/connecting rod
81074
81075
81076
Set connecting rod
81268
7
|
Maintenance
7.1 Preparation
WARNING
Before starting any work on the compressor:
Switch off the compressor and secure it to prevent a restart.
Relieve compressor of system pressure.
Prevent air from infiltrating the system!
After maintenance has been performed:
Connect safety switch.
Evacuate compressor.
Release switch-on lock.
7.2 Work to be carried out
In order to guarantee optimum operational reliability and service life of the compressor,
we
recommend
carrying out servicing and inspection work at regular intervals:
Oil change:
-
not mandatory for factory-produced series systems.
-
for field installations or when operating near the application limit: for the first time after 100
to 200 operating hours, then approx. every 3 years or 10,000 - 12,000 operating hours.
Dispose of used oil according to the regulations; observe national regulations.
Annual checks:
Oil level, leak tightness, running noises, pressures, temperatures, function of
auxiliary devices such as oil sump heater, pressure switch.