Capacity control steps
Compressor
type
Capacity %
20
Cylinders
Solenoids
87
(5+6) + 7 + (2+4) + (1+3)
1 + 3 + 4
100
(5+6) + 7 + 8 + (2+4) +
(1+3)
1 + 2 + 3 + 4
V 1800
Before Sept. 2014
20
(7+8)
-
30
(7+8) + 5
1
40
(7+8) + 5 + 6
1 + 2
50
(7+8) + 6 + (9+10)
2 + 3
60
(7+8) + 5 + 6 + (9+10)
1 + 2 + 3
70
(7+8) + 5 + (1+2+3+4)
1 +4
80
(7+8) + 5 + 6 + (1+2+3+4)
1 + 2 + 4
90
(7+8) + 6 + (9+10) + (1+2+3+4)
2 + 3 + 4
100
(7+8) + 5 + 6 + (9+10) +
(1+2+3+4)
1 + 2 + 3 + 4
V 1800
From Sept. 2014
30
(5+7+8)
-
40
(5+7+8) + 6
4
50
(5+7+8) + (9+10)
1
60
(5+7+8) + (9+10) + 6
1 + 4
70
(5+7+8) +(9+10) + (1+2)
1 + 2
80
(5+7+8) + 6 + (3+4) +
(1+2)
2 + 3 + 4
90
(5+7+8) + (3+4) + (9+10)
+ (1+2)
1 + 2 + 3
100
(5+7+8) + (3+4) + (9+10)
+ (1+2) + 6
1 + 2 + 3 + 4
4.5
DIAGRAMS TWO STAGE
Solenoid valve/cylinder numbering for electric capacity control
Compressor
type
Solenoid
UNL
NO
21
No. 1
NC
No. 2
NC
No. 3
NC
No. 4
NC
Cylinder number
22
/ solenoid valves
300T &
700T
[4
hp
]
1
2
3
-
450T &
1100T
[4
hp
]
1
2, 3
5, [6
hp
]
-
20
Refer to the swept volume expressed as a percentage of the full-load swept volume
21
UNL, Unloaded start
22
Numbers between brackets [] are HP cylinders
APPENDIX; Product Information (PI)
DIAGRAMS TWO STAGE
0089288gbr_11
30.10.2017
55
Содержание Grasso V Series
Страница 6: ...0089288gbr_11 6 30 10 2017 ...
Страница 8: ...0089288gbr_11 8 30 10 2017 ...
Страница 10: ...0089288gbr_11 10 30 10 2017 ...
Страница 61: ...Fig 16 Grasso V 6 Pre lubrication valve APPENDIX Product Information PI 0089288gbr_11 30 10 2017 61 ...