![GE WavePro WPS32SUBSH1 Скачать руководство пользователя страница 1](http://html.mh-extra.com/html/ge/wavepro-wps32subsh1/wavepro-wps32subsh1_installation-instructions_130396001.webp)
1
DEH-158 Installation Instructions R04
WavePro ™ Power Circuit Breakers
Key Lock Mounting Accessory Kit for 3200-4000A Substructure
Cat. No’s WPS32SUBSH1, WPS32SUBSH2, WPH32SUBSH1,
WPH32SUBSH2, WPS40SUBSH1, and WPS40SUBSH2
Fig. 1
WPSKLMTG2:
Item Qty Description
1
1
Slide Assembly
2
5
Tamper-resistant Screws (1/4-20 x .625)
3
5
Flat Washer
4
1
Mounting Plate
5
7
Lock Washer
6
2
Tamper-resistant Screws (1/4-20 x .500)
7
1
Taptite
8
1
Shim
9
1
Pivot Bar Assembly
Table 1. List of parts included in the key lock mounting kit
WPSKLMTG2.
KIT CONTENTS (Cat. No. WPSKLMTG2)
This kit shown above contains the retaining angle
with slide assembly, pivot bar assembly, mounting
plate, and mounting hardware. This unit installs on
the left side of the substructure. Key lock is
furnished by the customer. See back of this sheet
for lock required. Installation requires 5/32” tamper-
resistant hex wrench.
INSTRUCTIONS
1.
Remove parts as shown in Fig. 1.
2.
Assemble the customer supplied key lock to the
mounting plate (item #4) using 2 tamper-
resistant screws (item #6), lock washers (item
#5), and flat washers (item #3) as shown in Fig.
2.
3.
Mount the retaining angle with slide assembly
(item #1) to left side of substructure reusing 3
taptites as shown in Fig. 2. (Leave hardware
loose.)
4.
Attach key lock and mounting plate assembly to
the left side of the substructure using 3 tamper-
resistant screws (item #2) and lock washers
(item #5) as shown in Fig. 2. (Leave hardware
loose.)
5.
If needed, adjust fixed cam as shown in Fig. 3.
Screws may need to be loosened and roll pin
removed in order to make adjustment. Torque
hardware to 7-9 Ft-Lbs. Drill 0.1875 diameter
hole through the fixed cam and side frame.
Reuse and install roll pin.
6.
Insert pivot bar rivet into slide assembly slot and
mount to left side of substructure using shim
(item #8), 2 tamper resistant screws (Item #2),
CAUTION
: To avoid electrical hazard, make sure
primary and secondary circuits are not energized
while working in the compartment.