5.2
Configuring Racks and Slots
Even though a VersaMax PLC does not have a module rack, both autoconfiguration and
software configuration use the traditional convention of
racks
and
slots
to identify module
locations in the system. Each logical rack consists of the CPU or an Expansion Receiver
module plus up to 8 additional I/O and option modules mounted on the same DIN rail.
Each I/O or option module occupies a
slot
. The module next to the CPU or Expansion
Receiver module is in slot 1. Booster power supplies do not count as occupying slots.
1
Booster Power
Supply
CPU
2
3
4
5
Main Rack (rack 0)
The main rack is rack 0. Additional racks are numbered 1 to 7.
In a system that uses just one expansion rack which is attached to the expansion bus by a
non-isolated Expansion Receiver Module (IC200ERM002), the expansion rack must be
configured as rack 1.
PS
ERM
VersaMax Expansion Rack
1 M
VersaMax PLC Station Main Rack
PS
CPU/NIU
Configuration
GFK-1503E User Manual 71
For public disclosure
Содержание VersaMax PLC
Страница 1: ...GE Intelligent Platforms GFK 1503E VersaMax PLC User Manual September 2015 For public disclosure ...
Страница 16: ...Notes 16 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 38: ...Notes 38 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 50: ...Notes 50 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 92: ...Notes 92 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 112: ...Notes 112 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 224: ...Notes 224 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 292: ...Notes 292 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 316: ...Notes 316 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 317: ......
Страница 318: ...GE Intelligent Platforms 1 800 433 2682 1 434 978 5100 www ge ip com GFK 1503E For public disclosure ...