CE Mark Installation Requirements
The following requirements for surge, electrostatic discharge (ESD), and fast transient
burst (FTB) protection must be met for applications that require CE Mark listing:
•
The VersaMax PLC is considered to be open equipment and should therefore be
installed in an enclosure (IP54).
•
This equipment is intended for use in typical industrial environments that utilize
anti-static materials such as concrete or wood flooring. If the equipment is used in an
environment that contains static material, such as carpets, personnel should discharge
themselves by touching a safely grounded surface before accessing the equipment.
•
If the AC mains are used to provide power for I/O, these lines should be suppressed
prior to distribution to the I/O so that immunity levels for the I/O are not exceeded.
Suppression for the AC I/O power can be made using line-rated MOVs that are
connected line-to-line, as well as line-to-ground. A good high-frequency ground
connection must be made to the line-to-ground MOVs.
•
AC or DC power sources less than 50V are assumed to be derived locally from the
AC mains. The length of the wires between these power sources and the PLC should
be less than a maximum of approximately 10 meters.
•
Installation must be indoors with primary facility surge protection on the incoming
AC power lines.
•
In the presence of noise, serial communications could be interrupted.
68
GFK-1503E
VersaMax PLC User Manual
For public disclosure
Содержание VersaMax PLC
Страница 1: ...GE Intelligent Platforms GFK 1503E VersaMax PLC User Manual September 2015 For public disclosure ...
Страница 16: ...Notes 16 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 38: ...Notes 38 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 50: ...Notes 50 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 92: ...Notes 92 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 112: ...Notes 112 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 224: ...Notes 224 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 292: ...Notes 292 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 316: ...Notes 316 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 317: ......
Страница 318: ...GE Intelligent Platforms 1 800 433 2682 1 434 978 5100 www ge ip com GFK 1503E For public disclosure ...