11.7
Change/Read Number of Words to Checksum
Use SVCREQ 6 to read or change the number of words in the program to be
checksummed. The function is successful unless some number other than 0 or 1 is entered
as the requested operation.
11.7.1
Parameter Block Formats for SVCREQ 6
The parameter block has a length of 2 words.
To read the word count, the first word of the parameter block must contain a zero:
address
0 (read word count)
a 1
ignored
The function returns the current word count in the second word of the parameter block.
address
0
a 1
current word count
To change the word count, the first word of the parameter block must contain a one:
address
1 (change word count)
a 1
new word count (0 to 32)
The PLC will change the number of words to be checksummed to the new value.
The Service Request Function
GFK-1503E User Manual 203
For public disclosure
Содержание VersaMax PLC
Страница 1: ...GE Intelligent Platforms GFK 1503E VersaMax PLC User Manual September 2015 For public disclosure ...
Страница 16: ...Notes 16 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 38: ...Notes 38 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 50: ...Notes 50 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 92: ...Notes 92 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 112: ...Notes 112 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 224: ...Notes 224 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 292: ...Notes 292 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 316: ...Notes 316 GFK 1503E VersaMax PLC User Manual For public disclosure ...
Страница 317: ......
Страница 318: ...GE Intelligent Platforms 1 800 433 2682 1 434 978 5100 www ge ip com GFK 1503E For public disclosure ...