6.3 METERING
6 ACTUAL VALUES
6
The metered values for real, reactive, and apparent power, as well as power factor, are displayed in this menu. The "SRC
1" text is replaced by whatever name was programmed by the user for the associated source (see
SETTINGS
SYSTEM
SETUP
SIGNAL SOURCES
).
When VTs are configured in wye, the T60 calculates power in each phase and three-phase power is measured as
S = V
A
x Î
A
+ V
B
x Î
B
+ V
C
x Î
C
(EQ 6.1)
When VTs are configured in delta, the T60 does not calculate power in each phase and three-phase power is measured as
S = V
AB
x Î
A
+ V
CB
x Î
C
(EQ 6.2)
where
S is the apparent power
V
A
, V
B
, V
C
, I
A
, I
B
, I
C
are phase voltage and phase current phasors
V
AB
and V
CB
are phase-to-phase voltage phasors
Î is the conjugate of I
g) ENERGY METERING
PATH: ACTUAL VALUES
METERING
SOURCE SRC 1
ENERGY
The metered values for real and reactive energy are displayed in this menu. The "SRC 1" text will be replaced by whatever
name was programmed by the user for the associated source (see
SETTINGS
SYSTEM SETUP
SIGNAL SOURCES
).
Because energy values are accumulated, these values should be recorded and then reset immediately prior to changing
CT or VT characteristics.
MESSAGE
SRC 1 APPARENT PWR
φ
a: 0.000 VA
MESSAGE
SRC 1 APPARENT PWR
φ
b: 0.000 VA
MESSAGE
SRC 1 APPARENT PWR
φ
c: 0.000 VA
MESSAGE
SRC 1 POWER FACTOR
3
φ
: 1.000
MESSAGE
SRC 1 POWER FACTOR
φ
a: 1.000
MESSAGE
SRC 1 POWER FACTOR
φ
b: 1.000
MESSAGE
SRC 1 POWER FACTOR
φ
c: 1.000
ENERGY
SRC 1
SRC 1 POS WATTHOUR:
0.000 Wh
MESSAGE
SRC 1 NEG WATTHOUR:
0.000 Wh
MESSAGE
SRC 1 POS VARHOUR:
0.000 varh
MESSAGE
SRC 1 NEG VARHOUR:
0.000 varh
Содержание UR T60
Страница 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 492: ...8 18 T60 Transformer Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 510: ...9 18 T60 Transformer Protection System GE Multilin 9 6 COMMISSIONING TEST TABLES 9 COMMISSIONING 9 ...
Страница 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Страница 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...