GE Multilin
T60 Transformer Protection System
5-179
5 SETTINGS
5.6 GROUPED ELEMENTS
5
•
XFMR HST PICKUP
: Enter the hottest-spot temperature required for operation of the element. This setting should be
based on the maximum permissible hottest-spot temperature under emergency transformer loading conditions and
maximum ambient temperature.
•
XFMR HST DELAY
: Enter an appropriate time delay before operation of the element.
Figure 5–92: TRANSFORMER HOTTEST-SPOT TEMPERATURE LOGIC
e) AGING FACTOR
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
TRANSFORMER
AGING FACTOR
The Aging Factor element detects transformer aging in per-unit normal insulation aging. The element can be set for alarm
or trip whenever the computed aging factor is greater than the user-defined pickup setting for the specified time delay.
•
AGING FACTOR PICKUP
: Enter a value above which the aging factor element will operate. The setting should be
greater than the maximum permissible aging factor under emergency loading conditions and maximum ambient tem-
perature.
Figure 5–93: AGING FACTOR LOGIC
AGING FACTOR
AGING FACTOR
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
AGING FACTOR PICKUP:
2.0 pu
Range: 1.1 to 10.0 pu in steps of 0.1
MESSAGE
AGING FACTOR
DELAY:
10 min.
Range: 0 to 30000 min. in steps of 1
MESSAGE
AGING FACTOR BLOCK:
Off
Range: FlexLogic™ operand
MESSAGE
AGING FACTOR TARGET:
Self-Reset
Range: Self-reset, Latched, Disabled
SETTING
SETTING
ACTUAL VALUE
SETTINGS
FLEXLOGIC OPERANDS
HOTTEST-SPOT t
FUNCTION:
°
HOTTEST-SPOT t
BLOCK:
°
HOTTEST-SPOT t
°
XFMR HST-SPOT t C OP
°
XFMR HST-SPOT t C DPO
°
XFMR HST-SPOT t C PKP
°
Disable=0
Enable=1
Off=0
HOTTEST-SPOT t
PICKUP:
°
HOTTEST-SPOT t
PICKUP TIME DELAY:
°
RUN
t C > PKP
°
t
PKP
828731A3.CDR
AND
SETTING
SETTING
ACTUAL VALUE
SETTINGS
FLEXLOGIC OPERANDS
AGING FACTOR
FUNCTION:
AGING FACTOR
BLOCK:
AGING FACTOR-FAA
FAA > PKP
t
PKP
RUN
AGING FACTOR
PICKUP DELAY:
AGING FACTOR
PICKUP:
AGING FACTOR OP
AGING FACTOR DPO
AGING FACTOR PKP
Disable=0
Enable=1
Off=0
828733A2.CDR
AND
Содержание UR T60
Страница 10: ...x T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 14: ...xiv T60 Transformer Protection System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Страница 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 436: ...5 298 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 492: ...8 18 T60 Transformer Protection System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 510: ...9 18 T60 Transformer Protection System GE Multilin 9 6 COMMISSIONING TEST TABLES 9 COMMISSIONING 9 ...
Страница 678: ...C 30 T60 Transformer Protection System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 688: ...D 10 T60 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Страница 700: ...E 12 T60 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...