2-20
L60 Line Phase Comparison System
GE Multilin
2.2 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
2.2.11 TYPE TESTS
TYPE TESTS
TEST
REFERENCE STANDARD
TEST LEVEL
Dielectric voltage withstand
EN60255-5
2.3 kV
Impulse voltage withstand
EN60255-5
5 kV
Damped oscillatory
IEC61000-4-18 / IEC60255-22-1
2.5 kV CM, 1 kV DM
Electrostatic discharge
EN61000-4-2 / IEC60255-22-2
Level 3
RF immunity
EN61000-4-3 / IEC60255-22-3
Level 3
Fast transient disturbance
EN61000-4-4 / IEC60255-22-4
Class A and B
Surge immunity
EN61000-4-5 / IEC60255-22-5
Level 3 and 4
Conducted RF immunity
EN61000-4-6 / IEC60255-22-6
Level 3
Power frequency immunity
EN61000-4-7 / IEC60255-22-7
Class A and B
Voltage interruption and ripple DC
IEC60255-11
12% ripple, 200 ms interrupts
Radiated and conducted emissions
CISPR11 / CISPR22 / IEC60255-25
Class A
Sinusoidal vibration
IEC60255-21-1
Class 1
Shock and bump
IEC60255-21-2
Class 1
Seismic
IEC60255-21-3
Class 1
Power magnetic immunity
IEC61000-4-8
Level 5
Pulse magnetic immunity
IEC61000-4-9
Level 4
Damped magnetic immunity
IEC61000-4-10
Level 4
Voltage dip and interruption
IEC61000-4-11
0, 40, 70, 80% dips; 250 / 300 cycle interrupts
Damped oscillatory
IEC61000-4-12
2.5 kV CM, 1 kV DM
Conducted RF immunity, 0 to 150 kHz
IEC61000-4-16
Level 4
Voltage ripple
IEC61000-4-17
15% ripple
Ingress protection
IEC60529
IP40 front, IP10 back
Cold
IEC60068-2-1
–40°C for 16 hours
Hot
IEC60068-2-2
85°C for 16 hours
Humidity
IEC60068-2-30
6 day, variant 1
Damped oscillatory
IEEE/ANSI C37.90.1
2.5 kV, 1 MHz
RF immunity
IEEE/ANSIC37.90.2
20 V/m, 80 MHz to 1 GHz
Safety
UL508
e83849 NKCR
Safety
UL C22.2-14
e83849 NKCR7
Safety
UL1053
e83849 NKCR
Содержание UR series
Страница 2: ......
Страница 4: ......
Страница 12: ...xii L60 Line Phase Comparison System GE Multilin TABLE OF CONTENTS ...
Страница 32: ...1 20 L60 Line Phase Comparison System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 54: ...2 22 L60 Line Phase Comparison System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 132: ...4 30 L60 Line Phase Comparison System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 438: ...7 8 L60 Line Phase Comparison System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 478: ...8 40 L60 Line Phase Comparison System GE Multilin 8 3 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 502: ...A 10 L60 Line Phase Comparison System GE Multilin A 1 PARAMETER LIST APPENDIXA A ...
Страница 584: ...B 82 L60 Line Phase Comparison System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 622: ...D 10 L60 Line Phase Comparison System GE Multilin D 1 PROTOCOL APPENDIXD D ...
Страница 634: ...E 12 L60 Line Phase Comparison System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...
Страница 642: ...F 8 L60 Line Phase Comparison System GE Multilin F 3 WARRANTY APPENDIXF F ...