GE Multilin
L90 Line Current Differential System
2-21
2 PRODUCT DESCRIPTION
2.4 SPECIFICATIONS
2
LINE CURRENT DIFFERENTIAL (87L)
Application:
2 or 3 terminal line, series compensated
line, tapped line, with charging current
compensation
Pickup current level:
0.20 to 4.00 pu in steps of 0.01
CT Tap (CT mismatch factor): 0.20 to 5.00 in steps of 0.01
Slope # 1:
1 to 50%
Slope # 2:
1 to 70%
Breakpoint between slopes: 0.0 to 20.0 pu in steps of 0.1
Zero-sequence current differential (87LG):
87LG pickup level:
0.05 to 1.00 pu in steps of 0.01
87LG slope:
1 to 50%
87LG pickup delay:
0.00 to 5.00 s in steps of 0.01
DTT:
Direct Transfer Trip (1 and 3 pole) to
remote L90
Operating Time:
1.0 to 1.5 power cycles duration
Asymmetrical channel delay compensation using GPS:
asymmetry up to 10 ms
In-zone transformer group compensation: 0 to 330° in steps of
30°Inrush inhibit level:1.0 to 40.0%f
0
in
steps of 0.1
Inrush inhibit mode:per-phase, 2-out-of-3, average
LINE CUR-
RENT DIFFERENTIAL TRIP LOGIC
87L trip:
Adds security for trip decision; creates 1
and 3 pole trip logic
DTT:
Engaged Direct Transfer Trip (1 and 3
pole) from remote L90
DD:
Sensitive Disturbance Detector to detect
fault occurrence
Stub bus protection:
Security for ring bus and 1½ breaker
configurations
Open pole detector:
Security for sequential and evolving
faults
RESTRICTED GROUND FAULT
Pickup:
0.005 to 30.000 pu in steps of 0.001
Dropout:
97 to 98% of pickup
Slope:
0 to 100% in steps of 1%
Pickup delay:
0 to 600.00 s in steps of 0.01
Dropout delay:
0 to 600.00 s in steps of 0.01
Operate time:
<1 power system cycle
PHASE/NEUTRAL/GROUND TOC
Current:
Phasor or RMS
Pickup level:
0.000 to 30.000 pu in steps of 0.001
Dropout level:
97% to 98% of pickup
Level accuracy:
for 0.1 to 2.0
CT:
±0.5% of reading or ±0.4% of rated
(whichever is greater)
for > 2.0
CT:
±1.5% of reading > 2.0
CT rating
Curve shapes:
IEEE Moderately/Very/Extremely
Inverse; IEC (and BS) A/B/C and Short
Inverse; GE IAC Inverse, Short/Very/
Extremely Inverse; I
2
t; FlexCurves™
(programmable); Definite Time (0.01 s
base curve)
Curve multiplier:
Time Dial = 0.00 to 600.00 in steps of
0.01
Reset type:
Instantaneous/Timed (per IEEE)
Curve timing accuracy
at 1.03 to 20 x pickup:
±3.5% of operate time or ±½ cycle
(whichever is greater) from pickup to
operate
PHASE/NEUTRAL/GROUND IOC
Pickup level:
0.000 to 30.000 pu in steps of 0.001
Dropout level:
97 to 98% of pickup
Level accuracy:
0.1 to 2.0
CT rating: ±0.5% of reading or ±0.4% of rated
(whichever is greater)
> 2.0
CT rating
±1.5% of reading
Overreach:
<2%
Pickup delay:
0.00 to 600.00 s in steps of 0.01
Reset delay:
0.00 to 600.00 s in steps of 0.01
Operate time:
<16 ms at 3
pickup at 60 Hz
(Phase/Ground IOC)
<20 ms at 3
pickup at 60 Hz
(Neutral IOC)
Timer accuracy:
±3% of operate time or ±1/4 cycle
(whichever is greater)
Содержание UR Series L90
Страница 14: ...xiv L90 Line Current Differential System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Страница 68: ...2 34 L90 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 138: ...4 30 L90 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 604: ...9 58 L90 Line Current Differential System GE Multilin 9 6 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Страница 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...