C.4 GENERIC SUBSTATION EVENT SERVICES: GSSE AND GOOSE
C
–
Set
CONFIG GSE 1 FUNCTION
to “Enabled”.
–
Set
CONFIG GSE 1 ID
to an appropriate descriptive string (the default value is “GOOSEOut_1”).
–
Set
CONFIG GSE 1 DST MAC
to a multicast address (for example, 01 00 00 12 34 56).
–
Set the
CONFIG GSE 1 VLAN PRIORITY
; the default value of “4” is OK for this example.
–
Set the
CONFIG GSE 1 VLAN ID
value; the default value is “0”, but some switches may require this value to be “1”.
–
Set the
CONFIG GSE 1 ETYPE APPID
value. This setting represents the Ethertype application ID and must match the
configuration on the receiver (the default value is “0”).
–
Set the
CONFIG GSE 1 CONFREV
value. This value changes automatically as described in IEC 61850 part 7-2. For
this example it can be left at its default value.
3.
Configure the data by making the following changes in the
PRODUCT SETUP
ÖØ
COMMUNICATION
ÖØ
IEC 61850 PROTO-
COL
Ö
GGIO1 STATUS CONFIGURATION
settings menu:
–
Set
GGIO1 INDICATION 1
to a FlexLogic™ operand used to provide the status of GGIO1.ST.Ind1.stVal (for example,
a contact input, virtual input, a protection element status, etc.).
The C70 must be rebooted (control power removed and re-applied) before these settings take effect.
The following procedure illustrates the reception configuration.
1.
Configure the reception dataset by making the following changes in the
PRODUCT SETUP
ÖØ
COMMUNICATION
ÖØ
IEC
61850 PROTOCOL
Ö
GSSE/GOOSE CONFIGURATION
ÖØ
RECEPTION
ÖØ
CONFIGURABLE GOOSE
Ö
CONFIGURABLE GOOSE
1
ÖØ
CONFIG GSE 1 DATASET ITEMS
settings menu:
–
Set
ITEM 1
to “GGIO3.ST.Ind1.q” to indicate quality flags for GGIO3 status indication 1.
–
Set
ITEM 2
to “GGIO3.ST.Ind1.stVal” to indicate the status value for GGIO3 status indication 1.
The reception dataset now contains a set of quality flags, a single point status Boolean value, and a floating point ana-
log value. This matches the transmission dataset configuration above.
2.
Configure the GOOSE service settings by making the following changes in the
INPUTS/OUTPUTS
ÖØ
REMOTE DEVICES
ÖØ
REMOTE DEVICE 1
settings menu:
–
Set
REMOTE DEVICE 1 ID
to match the GOOSE ID string for the transmitting device. Enter “GOOSEOut_1”.
–
Set
REMOTE DEVICE 1 ETYPE APPID
to match the Ethertype application ID from the transmitting device. This is “0” in
the example above.
–
Set the
REMOTE DEVICE 1 DATASET
value. This value represents the dataset number in use. Since we are using
configurable GOOSE 1 in this example, program this value as “GOOSEIn 1”.
3.
Configure the data by making the following changes in the
INPUTS/OUTPUTS
ÖØ
REMOTE INPUTS
ÖØ
REMOTE INPUT 1
settings menu:
–
Set
REMOTE IN 1 DEVICE
to “GOOSEOut_1”.
–
Set
REMOTE IN 1 ITEM
to “Dataset Item 2”. This assigns the value of the GGIO3.ST.Ind1.stVal single point status
item to remote input 1.
Remote input 1 can now be used in FlexLogic™ equations or other settings. The C70 must be rebooted (control power
removed and re-applied) before these settings take effect.
The value of remote input 1 (Boolean on or off) in the receiving device will be determined by the GGIO1.ST.Ind1.stVal value
in the sending device. The above settings will be automatically populated by the EnerVista UR Setup software when a com-
plete SCD file is created by third party substation configurator software.
C.4.5 ETHERNET MAC ADDRESS FOR GSSE/GOOSE
Ethernet capable devices each contain a unique identifying address called a Media Access Control (MAC) address. This
address cannot be changed and is unique for each Ethernet device produced worldwide. The address is six bytes in length
and is usually represented as six hexadecimal values (for example, 00 A0 F4 01 02 03). It is used in all Ethernet frames as
the ‘source’ address of the frame. Each Ethernet frame also contains a
destination
address. The destination address can
be different for each Ethernet frame depending on the intended destination of the frame.
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...