2-16
C70 Capacitor Bank Protection and Control System
GE Multilin
2.2 SPECIFICATIONS
2 PRODUCT DESCRIPTION
2
REMOTE OUTPUTS (IEC 61850 GSSE/GOOSE)
Standard output points:
32
User output points:
32
DIRECT OUTPUTS
Output points:
32
DCMA OUTPUTS
Range:
–1 to 1 mA, 0 to 1 mA, 4 to 20 mA
Max. load resistance:
12 k
Ω
for –1 to 1 mA range
12 k
Ω
for 0 to 1 mA range
600
Ω
for 4 to 20 mA range
Accuracy:
±0.75% of full-scale for 0 to 1 mA range
±0.5% of full-scale for –1 to 1 mA range
±0.75% of full-scale for 0 to 20 mA range
99% Settling time to a step change: 100 ms
Isolation:
1.5 kV
Driving signal:
any FlexAnalog quantity
Upper and lower limit for the driving signal: –90 to 90 pu in steps of
0.001
ETHERNET SWITCH (HIGH VOLTAGE, TYPE 2S)
Nominal DC voltage:
110 to 240 V DC
Minimum DC voltage:
88 V DC
Maximum DC voltage:
300 V DC
Input Current:
0.9 A DC maximum
Nominal AC voltage:
100 to 240 V AC, 0.26 to 0.16 A/26 to 39
VA at 50/60 Hz
Minimum AC voltage:
85 V AC, 0.31 A/22 VA at 50/60 Hz
Maximum AC voltage:
265 V AC, 0.16 A/42 VA at 50/60 Hz
Internal fuse:
3 A / 350 V AC, Ceramic, Axial SLO
BLO;
Manufacturer: Conquer; Part number:
SCD-A 003
ETHERNET SWITCH (LOW VOLTAGE, TYPE 2T)
Nominal voltage:
48 V DC, 0.31 A/15 W
Minimum voltage:
30 V DC, 0.43 A/16 W
Maximum voltage:
60 V DC
Internal fuse:
5 A / 350 V AC, Ceramic, Axial SLO
BLO;
Manufacturer: Conquer; Part number:
SCD-A 005
2.2.8 COMMUNICATIONS
RS232
Front port:
19.2 kbps, Modbus
®
RTU
RS485
1 or 2 rear ports:
Up to 115 kbps, Modbus
®
RTU, isolated
together at 36 Vpk
Typical distance:
1200 m
Isolation:
2 kV
ETHERNET (FIBER)
ETHERNET (10/100 MB TWISTED PAIR)
Modes:
10 MB, 10/100 MB (auto-detect)
Connector:
RJ45
SNTP clock synchronization error: <10 ms (typical)
PARAMETER
FIBER TYPE
10MB MULTI-
MODE
100MB MULTI-
MODE
1
1. UR-2S and UR-2T only support 100 Mb multi-
mode
Wavelength
820 nm
1310 nm
Connector
ST
ST
Transmit power
–20 dBm
–20 dBm
Receiver sensitivity
–30 dBm
–30 dBm
Power budget
10 dB
10 dB
Maximum input
power
–7.6 dBm
–14 dBm
Typical distance
1.65 km
2 km
Duplex
full/half
full/half
Redundancy
yes
yes
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...