GE Multilin
C70 Capacitor Bank Protection and Control System
5-125
5 SETTINGS
5.6 GROUPED ELEMENTS
5
e) PHASE CURRENT UNBALANCE
(ANSI 60P)
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
ÖØ
PHASE CURRENT
ÖØ
PHASE CURRENT UNBALANCE 1(3)
PHASE CURRENT
UNBALANCE 1
CUR UNBALCE 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
CUR UNBALCE 1 DIF
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
MESSAGE
CUR UNBALCE 1 BANK
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
MESSAGE
CUR UNBALCE 1 INHNT
FACTOR A: 0.0000
Range: –0.1000 to 0.1000 in steps of 0.0001
MESSAGE
CUR UNBALCE 1 INHNT
FACTOR B: 0.0000
Range: –0.1000 to 0.1000 in steps of 0.0001
MESSAGE
CUR UNBALCE 1 INHNT
FACTOR C: 0.0000
Range: –0.1000 to 0.1000 in steps of 0.0001
MESSAGE
CUR UNBALCE 1 STG 1A
PICKUP: 0.020 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 2A
PICKUP: 0.030 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 3A
PICKUP: 0.040 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 4A
PICKUP: 0.050 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 1B
PICKUP: 0.020 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 2B
PICKUP: 0.030 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 3B
PICKUP: 0.040 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 4B
PICKUP: 0.050 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 1C
PICKUP: 0.020 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 2C
PICKUP: 0.030 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 3C
PICKUP: 0.040 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 4C
PICKUP: 0.050 pu
Range: 0.001 to 5.000 pu in steps of 0.001
MESSAGE
CUR UNBALCE 1 STG 1
PKP DELAY: 30.00 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
CUR UNBALCE 1 STG 2
PKP DELAY: 10.00 s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
CUR UNBALCE 1 STG 3
PKP DELAY: 1.00 s
Range: 0.00 to 600.00 s in steps of 0.01
Содержание UR Series C70
Страница 2: ......
Страница 10: ...x C70 Capacitor Bank Protection and Control System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 C70 Capacitor Bank Protection and Control System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 124: ...4 30 C70 Capacitor Bank Protection and Control System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 344: ...5 220 C70 Capacitor Bank Protection and Control System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 396: ...8 18 C70 Capacitor Bank Protection and Control System GE Multilin 8 3 ENERVISTA SECURITY MANAGEMENT SYSTEM 8 SECURITY 8 ...
Страница 414: ...9 18 C70 Capacitor Bank Protection and Control System GE Multilin 9 1 OVERVIEW 9 THEORY OF OPERATION 9 ...
Страница 436: ...10 22 C70 Capacitor Bank Protection and Control System GE Multilin 10 4 SETTING EXAMPLE 10 APPLICATION OF SETTINGS 10 ...
Страница 547: ...GE Multilin C70 Capacitor Bank Protection and Control System B 79 APPENDIX B B 4 MEMORY MAPPING B ...
Страница 548: ...B 80 C70 Capacitor Bank Protection and Control System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 586: ...D 10 C70 Capacitor Bank Protection and Control System GE Multilin D 1 OVERVIEW APPENDIXD D ...
Страница 598: ...E 12 C70 Capacitor Bank Protection and Control System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...