6-22
T35 Transformer Protection System
GE Multilin
6.4 RECORDS
6 ACTUAL VALUES
6
A trigger can be forced here at any time by setting “Yes” to the
FORCE TRIGGER?
command. Refer to the
COMMANDS
CLEAR RECORDS
menu for information on clearing the oscillography records.
6.4.4 DATA LOGGER
PATH: ACTUAL VALUES
RECORDS
DATA LOGGER
The
OLDEST SAMPLE TIME
represents the time at which the oldest available samples were taken. It will be static until the log
gets full, at which time it will start counting at the defined sampling rate. The
NEWEST SAMPLE TIME
represents the time the
most recent samples were taken. It counts up at the defined sampling rate. If the data logger channels are defined, then
both values are static.
Refer to the
COMMANDS
CLEAR RECORDS
menu for clearing data logger records.
6.4.5 BREAKER MAINTENANCE
PATH: ACTUAL VALUES
RECORDS
MAINTENANCE
BREAKER 1(6)
There is an identical menu for each of the breakers. The
BKR 1 ARCING AMP
values are in units of kA
2
-cycles. Refer to the
COMMANDS
CLEAR RECORDS
menu for clearing breaker arcing current records. The
BREAKER OPERATING TIME
is
defined as the slowest operating time of breaker poles that were initiated to open.
DATA LOGGER
OLDEST SAMPLE TIME:
2000/01/14 13:45:51
MESSAGE
NEWEST SAMPLE TIME:
2000/01/14 15:21:19
BREAKER 1
BKR 1 ARCING AMP
φ
A:
0.00 kA2-cyc
MESSAGE
BKR 1 ARCING AMP
φ
B:
0.00 kA2-cyc
MESSAGE
BKR 1 ARCING AMP
φ
C:
0.00 kA2-cyc
MESSAGE
BKR 1 OPERATING TIME
φ
A: 0
ms
MESSAGE
BKR 1 OPERATING TIME
φ
B: 0
ms
MESSAGE
BKR 1 OPERATING TIME
φ
C: 0
ms
MESSAGE
BKR 1 OPERATING
TIME:
0 ms
Содержание T35 UR Series
Страница 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Страница 382: ...9 16 T35 Transformer Protection System GE Multilin 9 5 COMMISSIONING TEST TABLES 9 COMMISSIONING 9 ...
Страница 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Страница 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...