T35 Transformer Protection System
GE Multilin
5.4 SYSTEM SETUP
5 SETTINGS
5
h) DIFFERENTIAL AND RESTRAINT CURRENT CALCULATIONS
Differential and restraint currents are calculated as follows:
(EQ 5.20)
(EQ 5.21)
(EQ 5.22)
(EQ 5.23)
(EQ 5.24)
(EQ 5.25)
where
,
, and
are the phase differential currents and
,
, and
are the phase restraint currents.
i) TRANSFORMER WINDINGS BETWEEN TWO BREAKERS
When the relay is to protect a transformer with windings connected between two breakers, such as in a ring bus or breaker-
and-a-half station configuration, one of the methods for configuring currents into the relay presented below should be used
(see the Breaker-and-a-Half Scheme diagram in the Overview section of this chapter).
For this example it is assumed that winding 1 is connected between two breakers and winding 2 is connected to a single
breaker. The CTs associated with winding 1 are CTX, at 1200/5 A and CTY, at 1000/5 A. CTX is connected to current input
channels 1 through 3 inclusive and CTY is connected to current input channels 5 through 7 inclusive on a type 8H CT/VT
module in relay slot “F.” The CT2 on winding 2 is 5000/5 A and is connected to current input channels 1 through 4 inclusive
on a type 8F CT/VT module in relay slot “M”.
SETUP METHOD A (PREFERRED)
This approach is preferred because it provides increased sensitivity as the current from each individual set of CTs partici-
pates directly in the calculation of CT ratio mismatch, phase compensation, zero-sequence removal (if required) and the
differential restraint current. The concept used in this approach is to consider that each set of CTs connected to winding 1
represents a connection to an individual winding. For our example we consider the two-winding transformer to be a three-
winding transformer.
1.
Enter the settings for each set of CTs in the
SYSTEM SETUP
AC INPUTS
CURRENT BANK
settings menu.
PHASE CT F1 PRIMARY:
“1200 A”
PHASE CT F1 SECONDARY:
“5 A”
GROUND CT F1 PRIMARY:
“1 A” (default value)
GROUND CT F1 SECONDARY:
“1 A” (default value)
PHASE CT F5 PRIMARY:
“1000 A”
PHASE CT F5 SECONDARY:
“5 A”
GROUND CT F5 PRIMARY:
“1 A” (default value)
GROUND CT F5 SECONDARY:
“1 A” (default value)
PHASE CT M1 PRIMARY:
“5000 A”
PHASE CT M1 SECONDARY:
“5 A”
GROUND CT M5 PRIMARY:
“5000 A”
GROUND CT M5 SECONDARY:
“5 A”
2.
Configure source
n
(source 1 for this example) as the current from CTX in Winding 1 in the
SYSTEM SETUP
SIGNAL
SOURCES
SOURCE 1(6)
settings menu.
SOURCE 1 NAME:
“WDG 1X”
SOURCE 1 PHASE CT:
“F1”
SOURCE 1 GROUND CT:
“None”
SOURCE 1 PHASE VT:
“None”
SOURCE 1 AUX VT:
“None”
Id
A
I
A
c
1
[ ]
I
A
c
2
[ ] …
I
A
c
w
total
[
]
+
+
+
=
Id
B
I
B
c
1
[ ]
I
B
c
2
[ ] …
I
B
c
w
total
[
]
+
+
+
=
Id
C
I
C
c
1
[ ]
I
C
c
2
[ ] …
I
C
c
w
total
[
]
+
+
+
=
Ir
A
max
I
A
c
1
[ ]
I
A
c
2
[ ] …
I
A
c
w
total
[
]
,
, ,
(
)
=
Ir
B
max
I
B
c
1
[ ]
I
B
c
2
[ ] …
I
B
c
w
total
[
]
,
, ,
(
)
=
Ir
C
max
I
C
c
1
[ ]
I
C
c
2
[ ] …
I
C
c
w
total
[
]
,
, ,
(
)
=
Id
A
Id
B
Id
C
Ir
A
Ir
B
Ir
C
Содержание T35 UR Series
Страница 10: ...x T35 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Страница 48: ...2 18 T35 Transformer Protection System GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 314: ...5 192 T35 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 338: ...6 24 T35 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 350: ...7 12 T35 Transformer Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 366: ...8 16 T35 Transformer Protection System GE Multilin 8 2 CYBERSENTRY 8 SECURITY 8 ...
Страница 382: ...9 16 T35 Transformer Protection System GE Multilin 9 5 COMMISSIONING TEST TABLES 9 COMMISSIONING 9 ...
Страница 406: ...A 14 T35 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 540: ...D 10 T35 Transformer Protection System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIX D D ...
Страница 552: ...E 12 T35 Transformer Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 560: ...F 8 T35 Transformer Protection System GE Multilin F 3 WARRANTY APPENDIX F F ...