Chapter 1
– Introduction
GE Reason Switches
REASON SWITCHES-TM-EN-3
23
6
Compliance
The device has undergone a range of extensive testing and certification processes to
ensure and prove compatibility with all target markets. A detailed description of
these criteria can be found in the Technical Specifications chapter.
6.1
Standard Compliance
Compliance with the European Commission Directive on EMC and LVD is
demonstrated by self-certification against international standards.
6.2
EMC Compliance
Compliance with IEC 60255-26:2013 was used to establish conformity.
6.3
Product Safety
Compliance with IEC 60255-27:2013 was used to establish conformity.
Protective Class
IEC60255-27:2013 Protective Class 1. This equipment requires a protective conductor
(ground) to ensure user safety.
Installation category
IEC 60255-27:2013 Installation category III (Overvoltage Category III). Equipment in
this category is qualification tested at 5kV peak, 1.2/50 µS, 500 Ohms, 0.5 J, between
all supply circuits and ground, and also between independent circuits.
Environment
IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-30, IEC 60068-2-14, IEC 60255-21-1, IEC
60255-21-2. The equipment is intended for indoor use only. If it is required for use in
an outdoor environment, it must be mounted in a specific cabinet or housing which
will enable it to meet the requirements of IEC 60529 with the classification of degree
of protection IP54.
Содержание T1000
Страница 2: ......
Страница 11: ...Figure 97 T1000 dimensions 298 Figure 98 S2020 and S2024G dimensions 299...
Страница 12: ......
Страница 41: ...Chapter 3 Hardware Design GE Reason Switches REASON SWITCHES TM EN 3 41 Figure 4 S2024G Switch...
Страница 103: ...GE Reason Switches Chapter 4 Functions REASON SWITCHES TM EN 3 103 Figure 64 Data Monitor Flow Network...
Страница 256: ......
Страница 274: ......