GE StationPortal Скачать руководство пользователя страница 1

GE  

Intelligent Platforms

 

 

 

 

Production Support Device 

 

StationPortal*

 

IC760STA100

 

 

Hardware User’s Guide, GFK-2522A

 

 

February 2010 

Содержание StationPortal

Страница 1: ...GE Intelligent Platforms Production Support Device StationPortal IC760STA100 Hardware User s Guide GFK 2522A February 2010 ...

Страница 2: ...e the information contained herein does not purport to cover all details or variations in hardware or software nor to provide for every possible contingency in connection with installation operation or maintenance Features may be described herein which are not present in all hardware and software systems GE Intelligent Platforms assumes no obligation of notice to holders of this document with resp...

Страница 3: ...ity in content and test levels with that of CISPR 22 and based on this commonality testing to the each individual standard was deemed inappropriate The FCC requires the following note to be published according to FCC guidelines Note This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provi...

Страница 4: ...is unavailable Technical Support Email support ip ge com Customer Care Email customercare ip ge com Primary language of support English Europe the Middle East and Africa Online Technical Support www ge ip com support Phone 800 1 433 2682 EMEA Direct Dial 352 26 722 780 if toll free 800 option is unavailable or if dialing from a mobile telephone Technical Support Email support emea ip ge com Custom...

Страница 5: ...Ethernet Port 6 Serial Port 7 24V Discrete Input Port 8 Discrete Output Port 9 Horn 11 Configuration Reset Pushbutton 11 Lamps and Lenses 11 Pushbutton 11 Changeable Labels 11 Status Light 11 Hardware Configuration 12 Accessing the Configuration Menu 12 Configuration Parameters 14 StationPortal Device Driver 15 Error Handling 16 Troubleshooting Guidelines 18 StationPortal Specifications 19 Physica...

Страница 6: ......

Страница 7: ...l power supply input 100V 240V 50Hz 60Hz Three indicator lights Status indicators for each digital I O point Horn 90 dB Serial RS 232 Port Ethernet port 10 100 Mbps Three digital inputs on a 5 pin M12 female connector Three digital outputs on a 5 pin M12 male connector Momentary pushbutton Configuration over Ethernet Functional Compatibility Clients StationPortal is capable of communicating with a...

Страница 8: ...ible controls indicators and connectors Front View Input Status LEDs Top Light Right Light Output Status LEDs Horn Changeable Label Changeable Label Changeable Label Left Light Momentary Pushbutton MAC Address Label on side of unit 2 StationPortal Hardware User s Guide February 2010 GFK 2522A ...

Страница 9: ...Hardware Overview Bottom View GFK 2522A 3 ...

Страница 10: ...tal does not have an enclosure suitable for outdoor use For environmental requirements refer to page 20 Mounting Instructions Note Limit the number of times you remove and reinstall the unit Too many installations may damage the plastic enclosure 1 Install two M3 screws at a horizontal distance of 3 937 100mm apart at the required height 2 Mount the StationPortal on the two screws using mounting t...

Страница 11: ... at 1A is provided in the input line as a backup The power supply usually trips and goes into retry mode before the fuse blows There is no additional indication if the power supply fuse blows The fuse is not user replaceable Power Cord Retainer A clip is provided on the StationPortal unit to provide retention for a few types of power cords Warning Electrical Shock Hazard To avoid personal injury o...

Страница 12: ...ITY instance can support are described in the CIMPLICITY documentation The StationPortal I O is natively addressable in the Proficy HMI SCADA CIMPLICITY control and visualization product Communications Ports Ethernet Port The StationPortal unit provides a 10 100 Mbps Ethernet port IEEE802 3 with an RJ45 connector on the bottom of the enclosure An unshielded twisted pair UTP CAT 5 cable is the mini...

Страница 13: ...its Parity Configurable Even Odd None Stop Bits 1 not configurable Flow Control None not configurable Port Location and Pin Assignments Pin Assignments 1 NC 2 RXD1 3 TXD1 4 NC 5 Ground 6 NC 7 NC 8 NC 9 NC Note When StationPortal unit is configured to check Even or Odd parity and equipment at the other end of serial communication is configured for opposite parity setting few characters will be rece...

Страница 14: ...cation and Pin Assignments Pin Assignments 1 24 VDC for input devices 2 Input 2 3 0V for input devices 4 Input 1 5 Input 3 Typical 24 VDC Positive Logic Input Circuit 3 3V _ 3 3V Input Connector Field 24V Input Circuit CPU Input Specifications Inputs per Module 3 one group with a single common Rated voltage 24V DC Input Voltage Range 0 to 30 VDC Isolation Field to Frame Ground 1500 VAC for 1 minut...

Страница 15: ...3 Hz 120 240VAC nominal Isolation Field to Frame Ground 1500 VAC for 1 minute Output Characteristics 5 30VDC 5 24 VDC nominal Output Voltage 5 250VAC 47 to 63 Hz 120 240VAC nominal 10mA per point minimum 4A for 5 250VAC maximum resistive or general purpose 4A for 5 30VDC maximum resistive 2A pilot duty per output 5 to 30VDC 5 to 250VAC Output Current 2A lamp load per output 5 to 30VDC 5 to 250VAC ...

Страница 16: ...es a 7ms L R time constant DC inductive load or Cos φ 0 4 AC inductive load Suppression Circuits Relay contact life when switching inductive loads will approach resistive load contact life if suppression circuits are used Examples of typical suppression circuits for AC and DC loads are shown below The 1A 200V diode shown in the DC load typical suppression example is an industry standard 1N4935 The...

Страница 17: ...m counterclockwise Pushbutton The StationPortal provides an integrated momentary push button for use in your applications Changeable Labels There are slots for labels below the Right light indicator Left light indicator and Pushbutton You can change the labels for the Right and Left indicator lights and the pushbutton The dimensions of the label are 33 78 mm x 11 99 mm x 0 40 mm L x W x D To inser...

Страница 18: ...o any personal computer PC using an Ethernet cable Power up the StationPortal unit Open the command prompt window on PC by clicking on Start Run Type cmd in the dialog box At the command prompt type the following to access the configuration menu telnet IP address Example telnet 192 168 0 35 Where IP address is the IP address of the StationPortal unit The Default IP address of StationPortal is 192 ...

Страница 19: ...ardware Configuration If you do not know the IP address it can be reset to the default settings For details refer to the Default Settings section on page 22 StationPortal Configuration Menu GFK 2522A 13 ...

Страница 20: ...sh Horn Hold OUTPUT1 OFF OUTPUT2 OFF OUTPUT3 OFF The factory default settings for StationPortal are to turn the Top Light ON and all other outputs horn outputs 1 3 etc off Illuminating a light when communication isn t present allows the end user to distinguish between a loss of power and absence of communication Note Do not enter 2 as the default state of the Field outputs because they do not supp...

Страница 21: ...tationPortal is connected to a Gigabit Switch Controller or 10 100 Mbps switch controller Note When StationPortal is connected to a 10 100 Mbps switch controller or to a Gigabit switch with Auto negotiation mode disabled this parameter should be set to No This parameter should be set to Yes only when StationPortal is connected to a Gigabit switch controller with Auto negotiation mode enabled 0 No ...

Страница 22: ...stated otherwise the values of other outputs are determined by the user defined default configuration Note The displayed blink codes represent two digits as explained in the entries that follow A blink is accomplished by first illuminating the light for 500ms and then turning the light off for another 500ms If the horn is configured for blink beep state it will sound as the Top light is on and be ...

Страница 23: ...ur steps Serial Receive Buffer Overflow When the serial data rate received from serial input device is faster than device transmit rate to the client application Blink code 22 Blink the Top LED twice 2 Wait for 2sec Gap between 2 and 2 Blink the Top LED twice 2 Wait for 5sec Gap between error codes Repeat the above four steps Invalid OP Code When processor fetches invalid OP code No Blink code Sys...

Страница 24: ...nd Status LED is blinking Serial communication cable is connected properly with Null modem configuration Check baud rate and parity are set correctly in the hardware configuration menu Serial data is not received or transmitted in the client s application Check baud rate and parity are set correctly in the client s application Check StationPortal unit is powered on and Status LED is blinking Input...

Страница 25: ...rce for the StationPortal Peak inrush current may be higher for shorter durations Functional Serial Communication RS 232 Port EIA232C DB 9 Male Speed 2400 bps 4800 bps 9600 bps 19200 bps Parity Even Odd None Stop Bits 1 not configurable Flow Control None not configurable Mounting hardware 4 40 screw IEEE 802 3 protocol 10 BaseT 100 Base TX Auto negotiate Full or half duplex RJ45 connectors Two sta...

Страница 26: ...20 Rated temperature limits refer to the ambient air temperature immediately surrounding within 3 7 6 cm the StationPortal where it is mounted Provisions for remaining within the stated limits must be considered where additional external thermal loads are imposed on the StationPortal These could include large heat producing motor drives or power supplies in the same cabinet 20 StationPortal Hardwa...

Страница 27: ...ification by Underwriter s Laboratories to UL60950 1 1st Edition 2007 10 31 standard and equivalent CAN CSA C22 2 No 60950 1 07 March 2007 standard EMC Directive and Low Voltage Directive Compliance to harmonized standards EN55024 1998 A1 2001 A2 2003 and EN60950 1 2006 in accordance with European Directives Refer to Declaration of Conformity found on the Support website The agency approvals liste...

Страница 28: ...rnet subnet mask 255 255 255 0 3 Ethernet default gateway 192 168 0 1 4 Serial baud rate 19200 5 Parity for serial communications None 6 Default States for Outputs Right Light Left Light Top Light Horn and Outputs O1 O2 and O3 0010000 All outputs in OFF state except Top light ON 7 Keep alive time 3 sec 8 Gigabit Switch Yes Power On Values for above setting will be as per Last Saved values 22 Stati...

Страница 29: ...mask 14 F Factory default settings 22 Features 1 H Horn 11 I Inputs port 8 IP address 14 L Labels changing 11 Lenses changing 11 Load previous configuration 15 O Operation 6 Outputs port 9 suppression circuits 10 Overcurrent protection 5 Overview hardware 2 P Parity 14 Power up 5 Power on values 22 Q Quit without save 15 R Related documents 1 Reset 11 S Save and exit 15 Serial Baud rate 14 Parity ...