6–46
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
S1 RELAY SETUP
CHAPTER 6: SETPOINTS
W1 BKR OPEN COLOR
Range: Off, Red, Green, Orange
Default: Green
Allows the user to select the color of the LED indicator under Breaker Open conditions.
W1 BKR CLSD COLOR
Range: Off, Red, Green, Orange
Default: Red
Allows the user to select the color of the LED indicator under Breaker Closed conditions.
W2 BKR OPEN COLOR
Range: Off, Red, Green, Orange
Default: Green
Allows the user to select the color of the LED indicator under Breaker Open conditions.
W2 BKR CLSD COLOR
Range: Off, Red, Green, Orange
Default: Red
Allows the user to select the color of the LED indicator under Breaker Closed conditions.
Installation
PATH
:
SETPOINTS > S1 RELAY SETUP > INSTALLATION
RELAY NAME
Range: Feeder Name, Alpha-numeric (18 characters)
Default: Feeder Name
The RELAY NAME setting allows the user to uniquely identify a relay. This name will
appear on generated reports. This name is also used to identify specific devices which
are engaged in automatically sending/receiving data over the communications channel.
RELAY STATUS
Range: Not Ready, Ready
Default: Not Ready
Allows the user to activate/deactivate the relay. The relay is not operational when set to
"Not Ready."