RX3i PROFINET IO-Scanner User Manual 
GFK-2737F   

 

 
 
 

PACSystems* 
RX3i PROFINET  
IO-Scanner  
User Manual 

GFK-2737F

 

December 2016 

Содержание RX3i PROFINET

Страница 1: ...GE Automation Controls Programmable Control Products RX3i PROFINET IO Scanner User Manual GFK 2737F PACSystems RX3i PROFINET IO Scanner User Manual GFK 2737F December 2016 ...

Страница 2: ...luded herein Changes modifications and or improvements to equipment and specifications are made periodically and these changes may or may not be reflected herein It is understood that GE may make changes modifications or improvements to the equipment referenced herein or to the document itself at any time This document is intended for trained personnel familiar with the GE products referenced here...

Страница 3: ...3 2682 International Americas Direct Dial 1 780 420 2010 if toll free 800 option is unavailable Customer Care Email customercare ip ge com Primary language of support English Europe the Middle East and Africa Phone 800 1 433 2682 EMEA Direct Dial 420 239015850 if toll free 800 option is unavailable or if dialing from a mobile telephone Customer Care Email customercare emea ip ge com Primary langua...

Страница 4: ... 3 4 USB Port 6 1 3 5 Ethernet Port Connections 6 1 4 PROFINET Communications 7 1 4 1 Notes on Available PROFINET Controllers 7 1 4 2 Operations of the PROFINET Scanner 8 1 5 PROFINET Redundant Media 9 1 6 System Limits 10 1 7 Supported Modules Power Supplies and Backplanes 11 1 8 Glossary 16 1 9 Documentation 18 Chapter 2 LED Operation and Connector Details 19 2 1 Normal Operation of Individual L...

Страница 5: ...d 1 Using the SD Card 32 3 4 2 Method 2 Using the DCP Tool 32 3 5 SFP Modules for Ethernet Ports 33 3 6 External Switch VLAN Priority Settings 33 3 7 Installing the USB Port Driver 33 3 8 Firmware Updates 33 Chapter 4 Configuration 35 4 1 Configuration Overview 36 4 1 1 Basic Configuration Steps 36 4 1 2 Configuration Tool 36 4 2 Adding an IO Device to a PROFINET LAN 37 4 2 1 Adding an RX3i PROFIN...

Страница 6: ...ncy 54 5 2 3 Sampling Rate 54 5 2 4 Differences from Main CPU Rack 54 5 2 5 Output Control 55 5 3 Hot Swap of I O Modules 56 Chapter 6 Diagnostics 57 6 1 Configuration Faults 58 6 2 Version Information 59 6 3 Fatal Error Handling 60 6 4 Connection Troubleshooting 61 Appendix A PROFINET Specifications 63 A 1 PROFINET Protocol Support 63 A 2 Technical Data 63 A 3 Limitations 64 A 3 1 PACSystems Feat...

Страница 7: ...kplane showing Removable Plastic Knockout ___________________________________________30 Figure 6 Install Module into RX3i Backplane __________________________________________________________31 Figure 7 Remove Module from RX3i Backplane ________________________________________________________31 Figure 8 Select System Redundancy Parameters in PME_________________________________________________39 Fi...

Страница 8: ... for selecting SFP modules and network cabling and connectors Chapter 4 Configuration describes how to configure the RX3i PROFINET Scanner and its associated IO devices Chapter 5 Operations describes powering up and restarting the RX3i PROFINET Scanner the input status data replacing I O modules while scanning and how to update the firmware Chapter 6 Diagnostics describes configuration faults how ...

Страница 9: ...used for PROFINET communications 10 Mbps can be used for other types of Ethernet traffic such as PING Features of the RX3i PNS include Full programming and configuration services for all supported Series 90 30 and RX3i I O Modules using Proficy Machine Edition For a list of currently supported I O modules refer to the Important Product Information IPI document provided with the firmware version on...

Страница 10: ...Added footnotes tracking PNS firmware support for various features such as HART Pass Through Added note on support for Remote Get HART Device Information COMMREQ E Apr 2015 In Section 1 7 corrected data for IC695SPF010 in table D May 2014 In Section 4 2 5 Configuring Module Parameters added Universal Analog Input Module and Power Sync and Measurement Module and related rules to the table In Sectio...

Страница 11: ...e upgrades One Micro B connector USB 2 0 compliant running at Full speed 12 MHz SD Card Supports SD and SDHC cards PNS Status and Control Bits 32 input status bits and 32 output control bits PROFINET I O production rate ms I O Update Rate Configurable selections 1 2 4 8 16 32 64 128 256 or 512 ms Number of IP Addresses Five One per external port and one internal I O Station Maximum Limits Number o...

Страница 12: ...Chapter 1 Introduction GFK 2737F December 2016 5 1 3 RX3i PROFINET Scanner Controls and Indicators Figure 1 Front View IC695PNS001 ...

Страница 13: ... is reserved for future use 1 3 4 USB Port The USB Port is used for installing new firmware using the WinLoader tool 1 3 5 Ethernet Port Connections Each port on an RX3i PNS operates independently so devices that operate at different speeds and or duplex modes may be attached to the ports By default all ports including empty unconfigured SFP cages are set for Automatic which enables auto negotiati...

Страница 14: ...O Network is controlled by one or more PROFINET I O Controllers PROFINET I O Controllers may be GE products or third party products GE Automation and Control offers the following RX3i PROFINET Controllers IC695PNC001 this is a rack based intelligent module located in a slot of the host RX3i CPU rack The host CPU may be equipped with a maximum of four IC695PNC001 modules The IC695CPE330 provides an...

Страница 15: ...any qualified PROFINET I O Controller The RX3i PNS performs the following operations Consumes PROFINET IO Device configuration from the PROFINET IO Controller over the PROFINET network and applies it to its modules Scans input data from each module it manages and produces that data to the PROFINET IO Controller Consumes the output data that it receives from the PROFINET IO Controller and applies i...

Страница 16: ...with MRP MRP Operation for I O Update Rates of 16ms or Greater MRP Operation at I O Update Rates Less Than 16ms Minimum I O Rate When Configured in an MRP Ring Minimum I O Update Rates for Bumpless Operation in a Ring Topology Third party MRP Manager Use with PNC as MRP Client Ring Topology with One Controller Ring Topology with Multiple Controllers Setting Up Media Redundancy Protocol Media Redun...

Страница 17: ...ses four to six submodules two submodules for basic operation of the PNS module two built in port submodules that are always configured up to two additional port submodules one for each optional Ethernet port configured Other limitations such as the configuration and I O sizes are specific to the configuration options chosen Note that not every combination of options is supported in every system I...

Страница 18: ... Negative Logic 8 in IC693MDL635 16 Circuit Input 125 Vdc Positive Negative Logic 16 in IC693MDL645 16 Circuit Input 24 Vdc Positive Negative Logic 16 in IC693MDL646 16 Circuit Input 24 Vdc Positive Negative Logic Fast 16 in IC693MDL648 16 Circuit Input 48 Vdc Positive Negative Logic Fast 16 in IC693MDL654 32 Circuit Input 5 12 Vdc Positive Negative Logic 32 in IC693MDL655 32 Circuit Input 24 Vdc ...

Страница 19: ...rcuit Output 120 Vac 0 5A 16 out IC693MDL330 8 Circuit Output 120 240 Vac 2A 8 out IC693MDL340 16 Circuit Output 120 Vac 0 5A 16 out IC693MDL350 16 Circuit Output 120 240 Vac Isolated 16 out IC693MDL390 5 Circuit Output 120 240 Vac 2A Isolated 8 out IC693MDL730 8 Circuit Output 12 24 Vdc 2A Positive 8 out IC693MDL731 8 Circuit Output 12 24 Vdc 2A Negative 8 out IC693MDL732 8 Circuit Output 12 24 V...

Страница 20: ...it Output 12 24 Vdc 0 5A Positive 16 out IC694MDL741 16 Circuit Output 12 24 Vdc 1A Negative 16 out IC694MDL742 16 Circuit Output 12 24 Vdc 1A Positive 16 out IC694MDL752 32 Circuit Output 5 24 Vdc 0 5A Negative 32 out IC694MDL753 32 Circuit Output 12 24 Vdc 0 5A Positive 32 out IC694MDL754 32 Circuit Output with ESCP none IC694MDL758 32 Circuit Output 12 24 Vdc 0 5A Positive with ESCP2 none IC694...

Страница 21: ...93ALG392 8 Point Analog Current Voltage Output ALG OUT 8 IC694ALG390 2 Point Analog Voltage Output ALG OUT 2 IC694ALG391 2 Point Analog Current Output ALG OUT 2 IC694ALG392 8 Point Analog Current Voltage Output ALG OUT 8 IC695ALG704 4 Point Analog Current Voltage Output3 4 none IC695ALG708 8 Point Analog Current Voltage Output4 none IC695ALG728 8 Point Analog Current Voltage Output4 HART5 Support ...

Страница 22: ...wer Supply Modules IC695PSA040 Universal 120 240 Vac 125Vdc 40W Power Supply none IC695PSA140 Multifunctional 120 240 Vac 125Vdc 40W Power Supply none IC695PSD040 24Vdc 40W Power Supply none IC695PSD140 Multifunctional 24Vdc 40W Power Supply none Small Form Factor Pluggable SFP Modules IC695SPC100 10 100 1000Base T Copper SFP none IC695SPF002 100Base FX fiber 2km SFP none IC695SPF010 1000Base LX f...

Страница 23: ... data to be transferred the sequence of the transfers and the transfer cycle between a PROFINET IO Controller or IO Supervisor and a PROFINET IO Device IOCS PROFINET Input Output Consumer Status is transmitted on the PROFINET network to provide feedback on Input Data for an IO controller and Output Data for an IO device IOPS PROFINET Input Output Provider Status is transmitted on the PROFINET netw...

Страница 24: ...ch as alarms RTC Real Time Cyclic A PROFINET IO Mechanism used to exchange input and output data Send Clock Value between 1 and 128 inclusive in units of 31 25 µs equivalent to a range of 31 25 µs to 4 ms used to calculate the Update Period for a PROFINET cyclic data transfer between two devices see IOCR The Send Clock is the basis for all other scheduling parameters Send Offset The time to delay ...

Страница 25: ...K 2830 RX3i Manuals PACSystems RX3i System Manual GFK 2314 PACSystems RX3i PROFINET Controller Command Line Interface Manual GFK 2572 PACSystems RX3i Max On Hot Standby Redundancy User s Manual GFK 2409 PACSystems RX3i PROFINET Controller User Manual GFK 2571 PACSystems RX3i CEP PROFINET Scanner User Manual GFK 2883 PACSystems HART Pass Through User Manual GFK 2929 PACSystems RX3i PROFINET Scanner...

Страница 26: ...GFK 2737F December 2016 19 Chapter 2 LED Operation and Connector Details This chapter describes LEDs Ethernet Network Ports SD Card Slot USB Port ...

Страница 27: ...LED Status Green Blinking The corresponding network interface is active Off The corresponding network interface is not active 2 1 3 Status LED The STATUS LED stays green during normal operation LED LED Status Green On Normal operation Red Blinking A MAC address read from non volatile memory is invalid Ports with invalid MAC addresses remain disconnected from the Ethernet network 2 1 4 CONN LED The...

Страница 28: ...into port 2 1 6 Active LED The Active LED indicates the Scanner is connected to a PROFINET IO Controller that is controlling the I O data for the I O modules located in the same rack as the PNS001 LED LED Status Green On PNS is connected to a PROFINET I O Controller that is controlling IO Module IO data Off PNS is not connected to a PROFINET I O Controller or no established connection to an Active...

Страница 29: ...eshing the device list double clicking on the RX3i PNS module and clicking the Identify Device button on the PNS properties pop up window 2 1 8 3 Microprocessor Over Temperature If the maximum threshold temperature for the PNS s microprocessor is crossed the PNS goes into power saving mode While the PNS is in an over temperature condition the following blink patterns are alternated PORT 1 PORT 2 a...

Страница 30: ...ion failure OK LAN and STATUS LEDs blink green in unison 1 Hz Invalid firmware detected or firmware update initiated Module is waiting for firmware update Blink pattern continues during firmware update After the automatic update completes the LAN and STATUS LEDs blink Amber and the module resets which restarts the power up process STATUS and LAN LEDs blink green in unison 1 Hz Internal update in p...

Страница 31: ...ection parameters The PROFINET protocol can be sent and received over any or all of the four external ports Devices connected to the PROFINET Scanner ports should have Ethernet Autonegotiation enabled The Ethernet ports can be disabled to support requirements such as IT policies for unused ports Disabled ports do not establish a link on their Ethernet network RX3i PNS modules and other participati...

Страница 32: ...n installing an SD Card the label should face to the left with the write protect Lock switch to the bottom The card should enter easily and click when fully inserted The spring action will return the card back slightly from its fully depressed position Do not force the card into the slot as that can damage the unit To release the card press the card in again until it clicks and the spring action w...

Страница 33: ... Scanner can be used to connect a computer for firmware updates for the PROFINET Scanner The USB port accepts a standard USB cable USB Micro B Male to USB Type A Male not included The port must be set up before using it as described in Section 3 7 Installing the USB Port Driver Note The USB port is for firmware upgrades only It is not intended as a permanent connection ...

Страница 34: ...modules Pre Installation check Power Requirements Hot insertion and removal Removing the backplane knockout Module installation and removal Port connections Installing SFP devices Installing the USB Port Driver Firmware updates For additional information about system installation also refer to the PACSystems RX3i Systems Manual GFK 2314 ...

Страница 35: ...nd Controls will fully cooperate with you should such action be necessary After unpacking the RX3i equipment record all serial numbers Serial numbers are required if you should need to contact Customer Care during the warranty period All shipping containers and all packing material should be saved should it be necessary to transport or ship any part of the system Verify that all components of the ...

Страница 36: ...TITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I DIVISION 2 Warning EXPLOSION HAZARD WHEN IN HAZARDOUS LOCATIONS TURN OFF POWER BEFORE REPLACING OR WIRING MODULES Warning EXPLOSION HAZARD DO NOT CONNECT OR DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NON HAZARDOUS Warning EXPLOSION HAZARD USB PORT IS ONLY FOR USE IN NON HAZARDOUS LOCATIONS DO NOT USE ...

Страница 37: ...d up Refer to Section 5 3 Hot Swap of I O Modules For a full discussion of this topic refer to the Hot Insertion and Removal section in the PACSystems RX3i System Manual GFK 2314 3 3 3 Removing the Backplane Knockout The PNS can be installed in slot 1 or slot 2 of a 7 12 or 16 slot RX3i Universal Backplane IC695CHS007 CHS012 or CHS016 or in slot 6 of a 7 slot RX3i Universal Backplane It may not be...

Страница 38: ...ct the module to be sure it is properly seated Secure the bottom of the module to the backplane using the machine screws provided with the module 3 Tighten the heat sink screw on the front of the module in the threaded hole in the back plate to 6 in lbs 0 68 Nm using a flat tip screwdriver 3 3 5 Module Removal RX3i rack power must be turned off Figure 7 Remove Module from RX3i Backplane Loosen the...

Страница 39: ...diting Device Name files contained on the SD Card Storing an illegal name to the RX3i PNS will prevent it from connecting to its PROFINET Controller until a valid Device Name is stored 3 4 1 Method 1 Using the SD Card 1 Remove power from the PNS module This should be done before network cabling is removed especially in the case of fiber connections 2 Remove network cabling from the module 3 Remove...

Страница 40: ... that has not passed Windows Logo testing This warning should be ignored Because each PNS has a different serial number the operating system recognizes each driver installation as different 3 8 Firmware Updates Note The RX3i PNS does not prevent initiation of firmware update when it is actively connected to an I O Controller When the PNS enters firmware update mode the PNS and its modules go to th...

Страница 41: ......

Страница 42: ...the Logic Developer online help This chapter discusses the following topics Configuration Overview o Basic Configuration Steps o Configuration Tools Adding an RX3i PROFINET Scanner to a LAN Configuring RX3i PROFINET Scanner Adding RX3i Modules to a Remote Node o Adding a Power Supply o Adding and Configuring an Ethernet Port o Configuring Module Parameters o Configuring Analog Modules that have DI...

Страница 43: ...r s recommended PROFINET I O configuration tool Configure the parameters of the PROFINET I O Controller Add IO Devices to the LAN PROFINET Scanners and other types of IO Devices use GSDML files to describe their capabilities The PROFINET I O configuration tool imports these GSDML files and incorporates the devices into the configuration Configure the parameters of the RX3i PROFINET Scanner Configu...

Страница 44: ...2 as its head end For product details refer to the VersaMax PROFINET Scanner Manual GFK 2721 4 2 1 Adding an RX3i PROFINET Scanner to the PROFINET LAN Begin this process by importing the GSDML file corresponding to the PNS001 module and its associated RX3i I O Rack Seven versions of this GSDML file are available based 1 on the size of the host RX3i I O Rack backplane and 2 upon which slot in that ...

Страница 45: ...teway 0 0 0 0 0 0 0 0 0 0 0 0 Note that if the PNS is subsequently power cycled without a PNC connected the PNS will power up with the default network settings because network settings configured by the PNC are not retentive In order to maintain settings over a power cycle without a PNC connected the network settings assigned by the PNC must match the network settings configured with the DCP Tool ...

Страница 46: ...he CPU s I O transfer list Note that once the HSB CPU Redundancy Mode is set Proficy Machine Edition automatically expands the Primary CPU s input transfer list to include all redundantly controlled PROFINET inputs as reference addresses are being assigned Proficy Machine Edition also automatically expands the Primary CPU s output transfer list to include all redundantly controlled PROFINET output...

Страница 47: ...ot be placed in the last non expansion slot of a rack Adding power supplies to the configuration sets up power supply alarms Loss of Module alarms will be triggered if the power supply is configured but not working or configured in the wrong subslot These power supplies have no configurable parameters but their power supply and GSDML details can be viewed by double clicking on a power supply icon ...

Страница 48: ...nection For example if no SFP modules are present and a configuration is attempted which disables the two built in RJ45 ports that configuration does not connect A configuration which disables the two built in RJ45 ports but has an SFP module configured which is not present also does not connect In this last example once an SFP module is installed in the specified port the port will become present...

Страница 49: ...rror on the module until its submodule level configuration has been completed as described below Figure 10 Analog Module with Configurable Parameters To complete this level of configuration right click the slot containing the I O Module and select Change Submodule List This opens a dialog box that presents a list of submodule options For example an analog module which employs jumpers to determine ...

Страница 50: ...f controls which are activated by a choice made outside of the group and marked with expander controls Typically this choice is directly preceding the first group Figure 11 Analog Module with Multiple Possible Option Settings Whenever multiple options are available only those parameters associated with the active choice are used The other settings are maintained but are ignored by the module To pr...

Страница 51: ...ltered during operation The module itself must experience a power cycle for an altered jumper setting to have effect 4 2 4 Support for Analog Modules with HART Features PNS001 firmware version 2 30 and later supports the HART Pass Through feature of a number of modules as listed in Section 1 7 HART compatible PNC001 and compatible RX3i CPU versions are also required Refer to the PACSystems HART Pa...

Страница 52: ...ted Thermocouple Input Module 12 Channel GFK 2500 IC695ALG412 Isolated High Speed Thermocouple Input Module 12 Channel GFK 2578 IC695ALG508 Analog Isolated RTD Input Module 8 Channel GFK 2501 IC695ALG600 Universal Analog Input Module 8 Channel GFK 2348 IC695ALG608 Analog Current Voltage Input Module 8 Channel GFK 2372 IC695ALG616 Analog Current VoltageInput Module 16 Channel GFK 2372 IC695ALG626 A...

Страница 53: ...ic reporting must be disabled when pulse testing is disabled 2 Auto Pulse Normal State and Auto Pulse Default State must not be equal to each other if pulse testing is enabled IC695ALG508 IC695ALG600 1 5 Same as C695ALG112 6 The Lead Resistance Compensation must be set to disabled for RTD 2 wire operation IC695ALG112 IC695ALG616 IC695ALG626 1 The High Scale Value Engineering Units cannot be equal ...

Страница 54: ...d the Range is set to a Voltage Range IC695HSC308 1 The counter High Range value must be greater than the Low Range Value 2 If a counter is configured as Continuous within high low range or One shot within high low range the PreLoad Value must alsobe within the range 3 If 1ms is selected as the Timebase Units the Timebase range is 1 to 429496 If units are 1 µS the range is 1 to 429496729 If units ...

Страница 55: ...hernet port settings such as port disabling This defaults all ports to Enabled with Auto negotiation on 4 3 1 Transferring the Device Name with an SD Card To allow replacement hardware to be commissioned without requiring a DCP Tool the PROFINET Device Name can be written to an SD Card and then transferred to replacement hardware via the SD Card To write the Device Name to an SD Card the SD Card m...

Страница 56: ...evice In the case of the IO Device being a PNS If all connections are lost the PNS retains the most recent configuration received since it was last powered up If a PNS has not been configured since being powered up it remains in its hardware default condition Whenever the PROFINET connection is re established and a configuration is sent to the PNS the PNS cross checks the configuration data if the...

Страница 57: ......

Страница 58: ...GFK 2737F December 2016 51 Chapter 5 Operations This chapter describes Power up I O Scanning Hot Swap of I O Modules Firmware Updates ...

Страница 59: ...or occurs during power up the amber OK LED blinks a unique pattern indicating the nature of the failure If the module encounters a hardware failure invalid firmware image or the power up diagnostics fail the module will not become operational or may enter firmware update mode Cycling power to the module may restore operation Refer to Section 6 3 Fatal Error Handling for more details Non volatile s...

Страница 60: ...s the health of the module A value of 0 indicates the module is powering up or has failed A value of 1 indicates the module is functioning properly 2 Reserved Set to 0 3 Port1 Link Up 1 port is connected to another device and is communicating 0 port is not connected to another device or the port has some sort of error preventing communications 4 Port2 Link Up 5 Port3 Link Up 6 Port4 Link Up 7 10 R...

Страница 61: ...ry events For example High Speed Counter Over Range Under Range Overflow and Underflow status conditions can be latched by configuring an unused counter to mirror the operating counter and assigning the event condition as a strobe source The corresponding strobe status and acknowledge bits may be used to monitor and acknowledge the condition 5 2 4 Differences from Main CPU Rack The following CPU o...

Страница 62: ...g Primary connection is lost and no matching Backup connection is established A Primary connection is lost if no message is received from the Primary IO Controller within a defined number of I O Update periods If the Primary connection is lost in PROFINET system redundancy but a matching Backup connection exists outputs are held at their last given value for a period of time to allow the Backup co...

Страница 63: ...e module does not match the configured module including any hardware setting such as a DIP Switch position a PROFINET Plug Wrong Submodule alarm is generated This appears as a System Configuration Mismatch PLC Fault in RX3i systems Fault Contacts corresponding to the mismatched module remain in the Fault on state If a module is inserted while the PNS has an established PROFINET connection and the ...

Страница 64: ...Chapter 6 Diagnostics GFK 2737F December 2016 57 Chapter 6 Diagnostics This chapter describes Configuration Faults Version Information Fatal Error Handling Connection Troubleshooting ...

Страница 65: ...per settings on the hardware and the physical settings do not match the configuration the PNS indicates a mismatch at the submodule level to the PNC which generates an alarm to the CPU When used with a PACSystems CPU a System Configuration Mismatch fault is reported and all point faults corresponding to the affected module will have the Fault Contact on If the physical module matches the configure...

Страница 66: ...tion is returned for the PNS slot with the information for the PROFINET Scanner Please consult the documentation for your IO Controller and configuration tool for how to access I M data For PACSystems PROFINET I O Controllers this is available under the Explore PROFINET Networks option in Proficy Machine Edition for details refer to this topic in the applicable PROFINET Controller User s Manual ...

Страница 67: ...EDs refer to Section 2 1 8 1 Fatal Error Codes Certain conditions can prevent the module from powering up and becoming operational or entering firmware update mode Problem Indication Action Hardware failure All LEDs off and the module is unresponsive or The STATUS LED is solid Green and is the only LED that is on Return the module to GE Automation and Controls Invalid firmware Power up diagnostics...

Страница 68: ...FINET so a simpler configuration might connect Invalid configurations will be rejected For example disabling all Ethernet ports would lead to significant problems so the connection with such a configuration is rejected outright Simplifying the configuration back to defaults can help isolate problem areas and settings PROFINET configuration occurs using the Ethernet IP settings If an IO Device cann...

Страница 69: ......

Страница 70: ... Remote Procedure Call LLDP Link Layer Discovery Protocol transmission only MRP Media Redundancy Protocol Client only A 2 Technical Data API Single API 0 used Number of Application Relations ARs supported 2 1 backup and 1 primary forming a redundant AR set or 1 simplex Maximum length of cyclic input data 1440 bytes Maximum length of output data 1440 bytes Alarm Types Pull Plug PlugWrong DCP Get Se...

Страница 71: ...gure In Run DCP Hello service DHCP Diagnostic Alarms DNS Domain Name Service protocol FastStartUp IRT Isochronous Real Time Protocol Multicast communication PROFIenergy Profile PROFIsafe Profile PROFINET CBA PTCP Precision Transparent Clock Protocol RT over UDP Shared I O device SNMP Simple Network Management Protocol Substitute Data Supervisor AR Only one Input CR and one Output CR are supported ...

Страница 72: ......

Страница 73: ...ble on our web site www geautomation com Additional Resources For more information please visit GE s Automation Controls web site www geautomation com Copyright 2013 2016 General Electric Company All Rights Reserved Trademark of General Electric Company All other brands or names are property of their respective holders GFK 2737F ...

Отзывы: