Chapter 4
– Configuration
RPV311
90
RPV311-TM-EN-7
Stream of data
Port number
1
4713
2
4714
3
4715
4
4716
In
Spontaneous
mode the RPV sends the PMU data automatically up to 4 different
socket addresses (IP + port number). All 4 destination configuration can be set as
unicast or multicast transmission.
The parameters of the Communication screen are listed below:
<C
OMMANDED
> Sets the respective streams of data to Commanded mode. When set to
Commanded mode. The RPV311 can send the HDR, CFG2 and CFG3 frames
according to the client’s IED request.
<S
PONTANEOUS
> Sets the respective streams of data to Spontaneous mode. When in
Spontaneous mode it is also possible to select which CFG frame the PMU will use. The
options are CFG2 and CFG3, at least one of them must be set. Additionally, it is
possible to choose if the HDR frame will be sent.
<U
NICAST
> Sets the addressing of the respective streams of data to Unicast mode.
This kind of transmission connects to a single IP address and the routing of the
messages though the available Ethernet ports are managed by the RPV system. It is
important that the destination IP and the RPV311 share the same subnetwork
address.
<M
ULTICAST
> Sets the addressing of the respective streams of data to Multicast mode.
This mode required the user to choose which Ethernet interface the RPV shall use to
convey the data.
18
MODBUS
Status, analog and digital data are available in MODBUS registers.
Access to SCADA integration is provided over the Ethernet interface. Up to 8
simultaneous connections are allowed a maximum rate of 60 accesses per second.
For further information about MODBUS, see Chapter 9: MODBUS.
Each register reports 16-bit data. Registers are divided into 3 groups:
Registers groups
0
Status
100 to 199
Analog data
200 to 223
Digital channels
Содержание RPV311
Страница 2: ......
Страница 44: ......
Страница 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Страница 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Страница 104: ...Chapter 5 Operation RPV311 104 RPV311 TM EN 7 Figure 49 Records monitoring sequence harmonics flicker and SOE ...
Страница 106: ...Chapter 5 Operation RPV311 106 RPV311 TM EN 7 Figure 50 Equipment settings monitoring sequence ...
Страница 107: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 107 Figure 51 Circuit and channel settings monitoring sequence ...
Страница 108: ...Chapter 5 Operation RPV311 108 RPV311 TM EN 7 Figure 52 Relays PMU and MODBUS settings monitoring sequence ...
Страница 110: ...Chapter 5 Operation RPV311 110 RPV311 TM EN 7 Figure 53 General information monitoring sequence ...
Страница 142: ......
Страница 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Страница 152: ......
Страница 160: ......
Страница 162: ......
Страница 164: ......
Страница 204: ......
Страница 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Страница 275: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 275 Figure 143 RA331 RA332 and RA333 dimensions ...
Страница 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...