RPV311
Chapter 6
– Records
RPV311-TM-EN-7
135
Derived measurements are continuously recorded. A new record is created at each
hour rollover. The record size depends on the number of derived measurements
selected by the user (limited to 64).
By trigger:
The disturbance recorder can be triggered by a Boolean equation, by a cross-trigger
signal of another recorder, by a manual trigger using the Web Interface, or by the
triggering of the fault recorder. It is possible to select the derived quantity of
triggered disturbance records. If the quantities are not manually selected, the record
will consist of all the quantities available for measurement. The record size depends
of the number of derived measurements selected by the user.
Continuous and triggered disturbance records share the same mass storage area.
2.1
Recorded Values
The following values are recorded by the continuous and triggered disturbance
recorders:
RMS value of voltage and current circuits;
Voltage and current phasors;
Frequency of voltage circuits;
Positive sequence of voltage and current circuits;
Negative sequence of voltage and current circuits;
Imbalance of voltage and current circuits;
Total harmonic distortion of voltage and current circuits;
Apparent combined power of power circuits;
Apparent fundamental power of power circuits;
Active fundamental power of power circuits;
Reactive fundamental power of power circuits;
Digital channels (state of digital inputs and binary GOOSE messages).
2.2
Recording Times by Trigger
Once triggered, the following parameters are considered by the disturbance
recorder:
Parameter
Allowed values
Increment
Pre-fault time (
𝑡
pre
)
0 … 5 min
0.1 min
Post-fault time (
𝑡
pos
)
0 … 20 min
0.1 min
Maximum Record
time
(
𝑡
max
)
1 … 20 min
0.1 s
Содержание RPV311
Страница 2: ......
Страница 44: ......
Страница 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Страница 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Страница 104: ...Chapter 5 Operation RPV311 104 RPV311 TM EN 7 Figure 49 Records monitoring sequence harmonics flicker and SOE ...
Страница 106: ...Chapter 5 Operation RPV311 106 RPV311 TM EN 7 Figure 50 Equipment settings monitoring sequence ...
Страница 107: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 107 Figure 51 Circuit and channel settings monitoring sequence ...
Страница 108: ...Chapter 5 Operation RPV311 108 RPV311 TM EN 7 Figure 52 Relays PMU and MODBUS settings monitoring sequence ...
Страница 110: ...Chapter 5 Operation RPV311 110 RPV311 TM EN 7 Figure 53 General information monitoring sequence ...
Страница 142: ......
Страница 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Страница 152: ......
Страница 160: ......
Страница 162: ......
Страница 164: ......
Страница 204: ......
Страница 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Страница 275: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 275 Figure 143 RA331 RA332 and RA333 dimensions ...
Страница 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...