1–18
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 1: OVERVIEW
Swell:
Pickup level: ..............................................1.01 to 1.50
×
VT in steps of 0.01
Dropout level: ...........................................pickup – 10% of nominal
1.6.7
System
COMMUNICATIONS
COM1/2: .........................................................RS485 2-wire, half duplex, isolated
COM3:..............................................................RS232 9-pin
Baud rate:......................................................1200 to 19200
Protocols:.......................................................Modbus
®
RTU; DNP 3.0
Functions:......................................................Read/write setpoints, read actual values, execute
commands, read device status
loopback test
CLOCK
Accuracy:.......................................................±1 min. / 30 days at 25±5°C
Resolution:.....................................................1 sec.
CONTROL POWER
Input:................................................................90 to 300 V DC or 70 to 265 V AC at 50/60 Hz
Power: .............................................................nominal 10 VA, max. 20 VA
Holdup: ...........................................................100 ms typical (at 120 V AC / 125 V DC)
It is recommended that the PQMII be powered up at least once per year to avoid
deterioration of the electrolytic capacitors in the power supply.
FUSE TYPE/RATING
5
×
20mm, 2.5 A, 250V
Slow blow, High breaking capacity
1.6.8
Testing and Approvals
TYPE TESTS
TEST
REFERENCE STANDARD
TEST LEVEL
Dielectric voltage withstand
2300-3700VAC
Impulse voltage withstand
EN60255-5
5KV
Insulation resistance
500VDC >100mohm
Damped Oscillatory
IEC61000-4-18IEC60255-22-1
2.5KV CM, 1KV DM
Electrostatic Discharge
EN61000-4-2/IEC60255-22-2
Level II
RF immunity
EN61000-4-3/IEC60255-22-3
10V/m 80-1Ghz
Fast Transient Disturbance
EN61000-4-4/IEC60255-22-4
Class A and B
Surge Immunity
EN61000-4-5/IEC60255-22-5
4Kv, 2KV
Conducted RF Immunity
EN61000-4-6/IEC60255-22-6
10Vrms
Radiated & Conducted Emissions
CISPR11 /CISPR22/ IEC60255-25
Class A
Содержание PQMII
Страница 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS...
Страница 12: ...1 4 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 1 OVERVIEW FIGURE 1 2 Feature Highlights...
Страница 19: ...CHAPTER 1 OVERVIEW PQMII POWER QUALITY METER INSTRUCTION MANUAL 1 11 FIGURE 1 9 Trace Memory Capture...
Страница 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION...
Страница 78: ...4 20 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE FIGURE 4 6 Voltage Disturbance Recorder...
Страница 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE...
Страница 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING...
Страница 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS...
Страница 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY...
Страница 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A...
Страница 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX...