6–16
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 6: MONITORING
•
FREQUENCY
: This message displays the frequency (in Hz). Frequency is calculated
from the phase A-N voltage (when setpoint
S2 SYSTEM SETUP
ÖØ
CURRENT/VOLTAGE
CONFIGURATION
ÖØ
VT WIRING
is “Wye”) or from phase A-B voltage (when setpoint
VT
WIRING
is “Delta”). A value of “0.00” is shown if there is insufficient voltage applied to
the PQMII’s terminals (less than 30 V on phase A).
•
FREQ MIN
: This message displays the minimum frequency measured as well as the
time and date at which the minimum frequency occurred.
•
FREQ MAX
: This message displays the maximum frequency measured as well as the
time and date at which the maximum frequency occurred.
6.2.8
Pulse Input Counters
PATH: ACTUAL VALUES
Ö
A1 METERING
ÖØ
PULSE INPUT COUNTERS
•
PULSE INPUT 1(4)
: These messages display the accumulated value based on total
number of pulses counted since the last reset. One switch input pulse is equal to the
value assigned in the
S2 SYSTEM SETUP
ÖØ
PULSE INPUT
ÖØ
PULSE INPUT 1(4) VALUE
setpoint.
The units shown after the value are as defined in the
PULSE INPUT UNITS
setpoint in the
same menu. The displayed value rolls over to “0” once the value “4294967295”
(FFFFFFFFh) has been reached. To use this feature, the “C” (control) option must be
installed and one of the PQMII switch inputs must be assigned to “Pulse Input 1(4)”
function. The switch input will then count the number of closures or openings
depending upon how the switch is configured; see
Switch Inputs
on page 5–21 for
details. The minimum timing requirements are shown in
.
•
PULSE IN 1+2+3+4
: The totalized pulse input value is displayed here. The pulse inputs
totalized is based on the
S2 SYSTEM SETUP
ÖØ
PULSE INPUT
ÖØ
PULSE INPUT TOTAL
setpoint.
•
TIME OF LAST RESET
: This message displays the time and date when the pulse input
values were last cleared. The
S1 PQMII SETUP
ÖØ
CLEAR DATA
ÖØ
CLEAR PULSE INPUT VALUES
setpoint clears the pulse input values.
PULSE INPUT
[
Z
]
COUNTERS
PULSE INPUT 1 =
0 Units
MESSAGE
PULSE INPUT 2 =
0 Units
MESSAGE
PULSE INPUT 3 =
0 Units
MESSAGE
PULSE INPUT 4 =
0 Units
MESSAGE
PULSE INPUT 1+2+3+4
= 0 Units
MESSAGE
TIME OF LAST RESET:
12:00:00am
01/01/95
Содержание PQMII
Страница 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS...
Страница 12: ...1 4 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 1 OVERVIEW FIGURE 1 2 Feature Highlights...
Страница 19: ...CHAPTER 1 OVERVIEW PQMII POWER QUALITY METER INSTRUCTION MANUAL 1 11 FIGURE 1 9 Trace Memory Capture...
Страница 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION...
Страница 78: ...4 20 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE FIGURE 4 6 Voltage Disturbance Recorder...
Страница 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE...
Страница 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING...
Страница 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS...
Страница 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY...
Страница 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A...
Страница 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX...