6–4
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 6: MONITORING
6.2
A1 Metering
6.2.1
Current Metering
PATH: ACTUAL VALUES
Ö
A1 METERING
ÖØ
CURRENT
•
A, B, C CURRENT
: Displays the current in each phase corresponding to the A, B, and C
phase inputs. Current will be measured correctly only if the
CT PRIMARY
is entered to
match the installed CT primary and the CT secondary is wired to match the 1 or 5 A
input. If the displayed current does not match the actual current, check this setpoint
and wiring.
•
Iavg/Vavg
: Displays the average of the three phase currents and three voltages. This
line is not visible if the
VT WIRING
setpoint is set to “Single Phase Direct”. L-N is displayed
when
VT WIRING
is set to “4 Wire Wye /3 VTs”, “4 Wire Wye Direct”, “4 Wire Wye / 2 VTs”,
or “3 Wire Direct”. L-L is displayed when
VT WIRING
is set to “3 Wire Delta / 2 VTs”.
CURRENT
[
Z
]
A = 100
B = 100
C = 100
AMPS
MESSAGE
Iavg =
100 AMPS
Vavg =
120 V L-N
MESSAGE
NEUTRAL CURRENT =
0 AMPS
MESSAGE
CURRENT UNBALANCE =
0.0%
MESSAGE
Ia MIN =
100 AMPS
12:00:00am
01/01/95
MESSAGE
Ib MIN =
100 AMPS
12:00:00am
01/01/95
MESSAGE
Ic MIN =
100 AMPS
12:00:00am
01/01/95
MESSAGE
In MIN =
100 AMPS
12:00:00am
01/01/95
MESSAGE
I U/B MIN =
0.0%
12:00:00am
01/01/95
MESSAGE
Ia MAX =
100 AMPS
12:00:00am
01/01/95
MESSAGE
Ib MAX =
100 AMPS
12:00:00am
01/01/95
MESSAGE
Ic MAX =
100 AMPS
12:00:00am
01/01/95
MESSAGE
In MAX =
100 AMPS
12:00:00am
01/01/95
MESSAGE
I U/B MAX =
0.0%
12:00:00am
01/01/95
Содержание PQMII
Страница 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS...
Страница 12: ...1 4 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 1 OVERVIEW FIGURE 1 2 Feature Highlights...
Страница 19: ...CHAPTER 1 OVERVIEW PQMII POWER QUALITY METER INSTRUCTION MANUAL 1 11 FIGURE 1 9 Trace Memory Capture...
Страница 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION...
Страница 78: ...4 20 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE FIGURE 4 6 Voltage Disturbance Recorder...
Страница 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE...
Страница 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING...
Страница 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS...
Страница 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY...
Страница 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A...
Страница 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX...