PQMII POWER QUALITY METER – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
•
SIMULATION ENABLED FOR
: Select the desired length of time to enable simulation.
When the programmed time has elapsed, current and voltage simulation will turn off.
If “Unlimited” is selected, simulated currents and voltages will be used until simulation
is turned off via the
SIMULATION
setpoint or via the serial port or until control power is
removed from the PQMII.
•
PHASE A/B/C/NEUTRAL CURRENT
: Enter the desired phase and neutral currents for
simulation.
•
Vax/Vbx/Vcx VOLTAGE
: Enter the desired voltages for simulation. The voltages
entered will be line or phase quantities depending upon the VT wiring type selected
with the
S2 SYSTEM SETUP
ÖØ
CURRENT/VOLTAGE CONFIGURATION
ÖØ
VT WIRING
setpoint.
•
PHASE ANGLE
: This setpoint represents the phase shift from a unity power factor.
Enter the desired phase angle between the current and voltage. The angle between
the individual currents and voltages is fixed at 120°.
5.6.3
Analog Outputs
PATH: SETPOINTS
ÖØ
S5 TESTING
ÖØ
ANALOG OUTPUTS SIMULATION
•
SIMULATION
: Enter “On” to switch from actual analog outputs to the programmed
simulated values. Set this setpoint “Off” after simulation is complete.
•
SIMULATION ENABLED FOR
: Select the desired length of time that simulation will be
enabled. When the programmed time has elapsed, analog output simulation will turn
off. If unlimited is selected, simulated analog outputs will be used until simulation is
turned off via the
SIMULATION
setpoint or via the serial port or until control power is
removed from the PQMII.
•
ANALOG OUTPUT 1(4)
: Enter the percentage of analog output to be simulated. The
output is 0 to 1 or 4 to 20 mA, depending upon the installed option.
For example, alter the setpoints below:
S5 TESTING
ÖØ
ANALOG OUTPUTS SIMULATION
ÖØ
ANALOG OUTPUT 1
: “50.0%”
S5 TESTING
ÖØ
ANALOG OUTPUTS SIMULATION
Ö
SIMULATION
: “On”
The output current level on Analog Output 1 will be 12 mA (4 to 20mA) or 0.5 mA (0 to 1mA).
ANALOG OUTPUTS
[
Z
]
SIMULATION
SIMULATION:
OFF
Range: Off, On
MESSAGE
SIMULATION ENABLED
FOR: 15
min
Range: 5 to 300 min. in steps of 5 or
UNLIMITED
MESSAGE
ANALOG OUTPUT 1:
OFF %
Range: 0.0 to 120.0% in steps of 0.1
MESSAGE
ANALOG OUTPUT 2:
OFF %
Range: 0.0 to 120.0% in steps of 0.1
MESSAGE
ANALOG OUTPUT 3:
OFF %
Range: 0.0 to 120.0% in steps of 0.1
MESSAGE
ANALOG OUTPUT 4:
OFF %
Range: 0.0 to 120.0% in steps of 0.1
Содержание PQMII
Страница 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS...
Страница 12: ...1 4 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 1 OVERVIEW FIGURE 1 2 Feature Highlights...
Страница 19: ...CHAPTER 1 OVERVIEW PQMII POWER QUALITY METER INSTRUCTION MANUAL 1 11 FIGURE 1 9 Trace Memory Capture...
Страница 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION...
Страница 78: ...4 20 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE FIGURE 4 6 Voltage Disturbance Recorder...
Страница 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE...
Страница 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING...
Страница 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS...
Страница 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY...
Страница 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A...
Страница 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX...