CHAPTER 5: SETPOINTS
PQMII POWER QUALITY METER – INSTRUCTION MANUAL
5–51
5.6
S5 Testing
5.6.1
Test Relays and LEDs
PATH: SETPOINTS
ÖØ
S5 TESTING
ÖØ
TEST RELAYS & LEDS
To verify correct operation of output relay wiring, each output relay and status indicator
can be manually forced on or off via the keypad or serial port.
While the
OPERATION TEST
setpoint is displayed, use the
VALUE
keys to scroll to the desired
output relay and/or status indicator to be tested. As long as the test message remains
displayed the respective output relay and/or status indicator will be forced to remain
energized. As soon as a new message is selected, the respective output relay and/or status
indicator return to normal operation.
5.6.2
Current/Voltage
PATH: SETPOINTS
ÖØ
S5 TESTING
ÖØ
CURRENT/VOLTAGE SIMULATION
Simulated currents and voltages can be forced instead of using actual currents or
voltages. This allows for verification of current and voltage related functions.
•
SIMULATION
: Enter “On” to switch from actual currents and voltages to the
programmed simulated values. Return to “Off” after simulation is complete.
TEST RELAYS &
[
Z
]
LEDS
OPERATION TEST:
NORMAL MODE
CURRENT/
[
Z
]
VOLTAGE SIMULATION
SIMULATION:
OFF
Range: Off, On
MESSAGE
SIMULATION ENABLED
FOR: 15
min
Range: 5 to 300 min. in steps of 5 or
UNLIMITED
MESSAGE
PHASE A CURRENT:
0 A
Range: 0 to 10000 A in steps of 1
MESSAGE
PHASE B CURRENT:
0 A
Range: 0 to 10000 A in steps of 1
MESSAGE
PHASE C CURRENT:
0 A
Range: 0 to 10000 A in steps of 1
MESSAGE
NEUTRAL CURRENT:
0 A
Range: 0 to 10000 A in steps of 1
MESSAGE
Vax VOLTAGE:
0 V
Range: 0 to 65000 V in steps of 1
MESSAGE
Vbx VOLTAGE:
0 V
Range: 0 to 65000 V in steps of 1
MESSAGE
Vcx VOLTAGE:
0 V
Range: 0 to 65000 V in steps of 1
MESSAGE
PHASE ANGLE:
0 DEGREES
Range: 0 to 359 degrees in steps of 1
Содержание PQMII
Страница 8: ...TOC VI PQMII POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS...
Страница 12: ...1 4 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 1 OVERVIEW FIGURE 1 2 Feature Highlights...
Страница 19: ...CHAPTER 1 OVERVIEW PQMII POWER QUALITY METER INSTRUCTION MANUAL 1 11 FIGURE 1 9 Trace Memory Capture...
Страница 58: ...3 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 3 OPERATION...
Страница 78: ...4 20 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE FIGURE 4 6 Voltage Disturbance Recorder...
Страница 84: ...4 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 4 SOFTWARE...
Страница 170: ...6 32 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 6 MONITORING...
Страница 196: ...7 26 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 7 APPLICATIONS...
Страница 198: ...8 2 PQMII POWER QUALITY METER INSTRUCTION MANUAL CHAPTER 8 WARRANTY...
Страница 208: ...A 10 PQMII POWER QUALITY METER INSTRUCTION MANUAL APPENDIX A...
Страница 216: ...B VIII PQM POWER QUALITY METER INSTRUCTION MANUAL CHAPTER B INDEX...