INSTRUCTIONS 

GEH-1023C 

TEST  BLOCKS 

AND 

PLUGS 

TYPE  PK-2 

INTRODUCTION 

The Type  PK -2  test  blocks  and plugs are  used 

to test  switchboard  mounted  instruments,  meters, 

and relays  when  in  an  electric  circuit  or  by the  use 

of 

a  separate  source of power.  They  are  available 

in either  four  or  six poles  and are back connected. 

The contacts  have line  contact. 

The  Type  PK-2  test  blocks  and plugs are  cap­

able of  carrying  10  amperes  at  250  volts  continu­

ously.  They  are not  intended  to  interrupt  any cur­

rent,  but  will  satisfactorily  open  the  circuit 

of 

potential  coil  and  transfer  the  current  coil 

of 

in­

struments,  meters,  or  relays. 

RECEIVING 

The  PK-2  test  blocks and plugs  are  shipped  in 

i n d i v i d u a l   cartons.  In  the  carton. with  the  test 

block,  una sse mbled in a  s e p a r  a t  e  container, are 

sufficient  auxiliary  contacts  for  a n y   combination 

shown  in  Fig.  8  and 

9. 

Also  p a c k e d  in  the  sep-

arate  c o n tai n e r  are  the  n u t s   and  washers  for 

the  studs;  m o u n t i n g  screws,  washers,  and nuts 

for  m o u n t i n g   the  test  block on steel panels;  and 

jumpers  a n d   holding  screws  for  the  a uxi l i a r y  

contacts. 

INSTALLATION 

MOUNTING 

The  block  can be  mounted on  the front surface 

of panels  1/8  inch  to  2  inches  thick  or on the rear 

surface  of  a  p a n  e 

not  more  than  1/8  inch  thick 

(see  Fig.  1 and  2}.  With  both methods 

of 

mounting, 

the  cover  and  test  plug  are  inserted  from  the  front 

of  the panel. 

Before  m o u n t i n  g  on  the pane 

I, 

the  auxiliary 

Fig. 

Mounting  on  Front  of  Steel  Panel 

contacts should be assembled according  to  the com­

bination  required,  as shown  in  Fig.  8 and 

9. 

Fig.  3  shows  a  composite  assembly 

of 

all  the 

auxiliary  contacts.  These  a r e   fastened  as shown 

by the  No.4-48,  5/16  inch round-head screws which 

pass through the auxiliary contacts  and  are  threaded 

into  the  inserts  in  the  bottom 

of 

the  block.  Auxil­

iary  contact  (1,  Fig.  3 ),  is  used  to  prevent  circuit 

interruption  when the cover  !s  removed.  This type 

I" 

Fig. 

Semi-Flush  Mounting  on  1/8-inch  Steel  Panel 

These  instructions  do  not  purport  to  cover  all  details  or  variations  in  equipment  nor  to  provide  for  every  possible 

contingency  to be  mel  in  connection  with  installation,  operation  or  maintenance.  Should  further  information  be  desired 

or  should  porticular  problems  arise 

which 

are not  covered sufficiently  for  the  purchaser's  purposes,  the  matter  should 

be 

referred  to  the  G-ral  Electric  Company. 

GENERAL

ELECTRIC 

www . ElectricalPartManuals 

. com 

www 

. ElectricalPartManuals 

. com 

Содержание PK-2

Страница 1: ...ING The block can be mounted on the front surface of panels 1 8 inch to 2 inches thick or on the rear surface of a p a n e 1 not more than 1 8 inch thick see Fig 1 and 2 With both methods of mounting the cover and test plug are inserted from the front of the panel Before m o u n t i n g on the paneI the auxiliary Fig I Mounting on Front of Steel Panel contacts should be assembled according to the ...

Страница 2: ...the size of the test block and panel mounting required in accordance with the dimensions shown in Fig 5 2 3 4 For ease of wiring and uniformity in testing the blocks should be mounted so the long center line is horizontalon the panel and the auxiliary contacts and interlocking slots are down CONNECTIONS Each b 1 o c k is essentially a multi pole jack When the cover is removed the device to be test...

Страница 3: ... plug a With cover in place and the plug contact in the cover making a connection through the block and remo g the short circuit by the auxiliary contact b With cover and plug removed used for circuit in which there is no current transformer c With the plug inserted and the plug contacts removing the short circuit by the auxiliary contact d With cover and plug removed and with auxiliary contact sh...

Страница 4: ... Spar e Relay for Protection While Testing Fig 16 Plug Connection for Fig II for Separate Test of Relay With Separate Source OPERATION e r m a n e n t connection of t h e Jl u g to the t e s t equipment is recommended With th e plugs properly connected there is little chance of er ror in testing as it is a matter of removing the cover of the block and inserting t h e proper test plug RENEWAL PARTS...

Отзывы: