HVDC TRANSFORMER BUSHINGS
PHI 530.1425.2500
PHI 265.850.1500
Kepco project
IS 2664 GB
Page
9
of
70
Bushing type
PHI 530.1425.2500
PHI 265.850.1500
Ambient conditions:
Max valve hall temperature
Min valve hall temperature
Max transformer oil temperature
+ 50
+5
+85
+ 50
+5
+85
°C
°C
°C
Pollution condition
Indoor
Very low
Very low
Minimum creepage distance
Indoor
>10080
>4125
mm
Minimum arcing distance
Indoor
>4728
>2994
mm
Seismic condition
0.225
0.225 g
Altitude above sea level (up to)
<1000
<1000 m
Installation angle
23°-33°
23-°40° From horizontal
Table 3 – Environmental conditions
5
Bushing preparation
All operators involved in components unpacking and assembly have to be careful not to damage the objects.
During the unpacking operation, it is necessary to check that all components supplied by GE Energy
Connections RPV are available and not damaged during the transportation.
All incoming goods must be stored in a covered area and prepared for the installation.
At the arrival, the crate must be inspected. Any damage of the crate or indication of the visual external shock
indicator (see
Figure 3
) must be reported to the Foreman and GE Energy Connections RPV Supervisor.
Figure 3 – Visual external shock indicator
A detailed control check list is listed in
Table 4
at
Paragraph 5.2
.
Содержание PHI 530.1425.2500
Страница 61: ...HVDC TRANSFORMER BUSHINGS PHI 530 1425 2500 PHI 265 850 1500 Kepco project IS 2664 GB Page 61 of 70...
Страница 62: ...HVDC TRANSFORMER BUSHINGS PHI 530 1425 2500 PHI 265 850 1500 Kepco project IS 2664 GB Page 62 of 70...
Страница 63: ...HVDC TRANSFORMER BUSHINGS PHI 530 1425 2500 PHI 265 850 1500 Kepco project IS 2664 GB Page 63 of 70...
Страница 64: ...HVDC TRANSFORMER BUSHINGS PHI 530 1425 2500 PHI 265 850 1500 Kepco project IS 2664 GB Page 64 of 70...