PanaFlow™ XMT1000 User’s Manual
1
Chapter 1. Installation
Chapter 1. Installation
1.1 Introduction
To ensure safe and reliable operation of the XMT1000, it must be installed in accordance with the established
guidelines. Those guidelines, explained in detail in this chapter, include the following topics:
•
Unpacking the XMT1000
•
Selecting the location for the XMT1000 (local or remote)
•
Installing the XMT1000 at the selected location
•
Wiring the XMT1000
1.2 CE Marking Compliance
For CE Marking compliance or installation in high noise areas, the XMT1000 flow transmitter must be wired in
accordance with the instructions in this section.
IMPORTANT:
CE Marking compliance is required for all units intended for use in EU countries.
The XMT1000 must be wired with the recommended cable, and all connections must be properly shielded and
grounded. Grounding of the chassis must be within 10 ft (3 m) of the transmitter. Refer to
below for the specific
requirements.
Note:
If the XMT1000 is wired as described above, the unit will comply with the EMC and LVD Directives.
WARNING!
The XMT1000 flow transmitter can measure the flow rate of many fluids, some of which
are potentially hazardous. The importance of proper safety practices cannot be overemphasized.
Be sure to follow all applicable local safety codes and regulations for installing electrical equipment
and working with hazardous fluids or flow conditions. Consult company safety personnel or local
safety authorities to verify the safety of any procedure or practice.
Attention European Customers!
To meet CE Marking requirements, all cables must be installed as
“CE Marking Compliance” on page 1
Table 1: Wiring Requirements
Connection
Cable Type
Ground Termination
Transducer
Armored RG-62 a/U or equivalent
Grounded using a cable gland.
Input/Output Armored 22 AWG shielded with armored material added to
outside of jacket
Grounded using a cable gland.
Power
Armored 14 AWG 2 conductor
Grounded using a cable gland.
Содержание PanaFlow XMT1000
Страница 1: ...GE Oil Gas Flow 910 313 Rev A June 2017 PanaFlow XMT1000 User s Manual ...
Страница 2: ......
Страница 4: ...ii no content intended for this page ...
Страница 8: ...Contents vi PanaFlow XMT1000 User s Manual no content intended for this page ...
Страница 12: ...Preface x PanaFlow XMT1000 User s Manual no content intended for this page ...
Страница 42: ...Chapter 3 Error Codes and Troubleshooting 30 PanaFlow XMT1000 User s Manual no content intended for this page ...
Страница 46: ...34 PanaFlow XMT1000 User s Manual no content intended for this page ...
Страница 68: ...Appendix C HART Communication 56 PanaFlow XMT1000 User s Manual no content intended for this page ...
Страница 95: ......