Hardware Installation
14
PACSystems* RXi Box IPC
GFK-2785C
Mounting Procedures
Using the optional ICRXIACCBPL Backplate, the IPC can be mounted on a DIN rail or a panel. You
can also mount the IPC directly onto a panel without using a Backplate.
The IPC has four captive machine screws in its base for attaching the unit to the Backplate or
panel.
Mounting the IPC on a DIN Rail
You will need the following:
One 2.5mm hex driver (included with the RXi IPC)
One flat
head
(or large Phillips) screwdriver
One Backplate, ICRXIACCBPL
When installed on the Backplate, the IPC mounts to a standard EN 50022 DIN rail with the
following dimensions.
Backplate Orientation
The Backplate should be installed with the static latches on top and the spring-loaded latches at
the bottom.
Backplate, Rear View
Static Latches (Top)
Spring-loaded Latches (Bottom)