GFK-2224Q
January 2017
135
Chapter 8
Modbus/TCP Server
This section describes the implementation of the Modbus/TCP Server feature for the PACSystems family of
products.
▪
Modbus/TCP Server
▪
Reference Mapping
▪
Modbus Function Codes
8.1
Modbus/TCP Server
The PACSystems products listed below support Modbus/TCP Server functionality:
▪
CPU010 and CPU020 with primary firmware version 3.0 or later.
▪
CRE020 with Ethernet firmware version 3.0 or later.
▪
RX7i: IC698ETM001 and RX3i IC695ETM001 with firmware version 3.0 or later.
▪
CRE305 and CRE310 with primary firmware version 7.30 or later
▪
Available on CPE330 Release 8.50.
▪
Available on all versions of CPE400.
Modbus/TCP Server Connections
The Modbus/TCP Server supports up to 16 simultaneous connections. These connections are not shared with
any other applications. Other TCP-based application protocols such as SRTP Server use a different set of TCP
connections.
Modbus Conformance Classes
PACSystems Modbus/TCP Server supports Modbus Conformance classes 0, 1, and 2.
The RX3i Ethernet module has been certified by the Modbus/TCP Conformance Test Laboratory to be in
conformance with
Conformance Test Policy
Version 2.1.
Server Protocol Services
The Modbus/TCP Server responds to incoming Request Connection, Terminate Connection and Request Service
messages. The client with which the server is interacting should wait for the server’s response before issuing
the next Request Service, otherwise requests could be lost.
There is no inactivity timeout in the server. If a client opens a connection, that connection stays open until the
connection is terminated.
Station Manager Support
The Modbus/TCP Server supports the standard Station Manager commands: STAT, TALLY, and TRACE, plus the
Modbus/TCP server-specific KILLMS command. The Modbus/TCP Server task letter is “o”.
8.2
Reference Mapping
The Modbus protocol’s reference table definition is different from the internal structure of the PACSystems
reference tables. Modbus refers to Holding Register, Input Register, Input Discrete and Coil tables; PACSystems
uses Discrete Input (%I), Discrete Output (%Q), Analog Input (%AI), Register (%R), and Word (%W) reference
Содержание PACSystems RX7i
Страница 45: ......
Страница 54: ...Chapter 4 Configuration GFK 2224Q January 2017 41 Figure 18 CPE400 Advanced Ethernet Configuration LAN1 LAN 2 ...
Страница 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Страница 81: ......
Страница 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Страница 142: ...Chapter 7 Programming SRTP Channel Commands GFK 2224Q January 2017 129 Figure 51 Sample Ladder Logic for COMMREQ ...
Страница 147: ......
Страница 193: ...Chapter 10 OPC UA Server 180 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q Example ...
Страница 202: ...Chapter 10 OPC UA Server GFK 2224Q January 2017 189 Figure 73 Machine Edition Online Command to Set Passwords ...
Страница 211: ......
Страница 253: ...Chapter 12 Diagnostics 240 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q ...
Страница 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Страница 263: ......