Chapter 5. PLC Hardware Configuration (Primary PLC) 

GFK-2928 

December 2017 

27 

5.6

 

Dual Bus Function Block 

The main function of the Dual Bus (

DBUS

) function block is to remap the discrete and analog inputs from the 

backup bus to the main bus by monitoring the status bits of the Genius devices that are installed on the dual 
bus pair. 

 

Figure 28: Dual Bus Function Block 

These are the external connections: 

 

Input 

DB

 

This receives the Genius bus parameters (via a variable of “

user defined type

” 

G_Bus

). Note that the 

parameters are configured using the function blocks derived from either 

INIT_GB00

 or 

INIT_GBnn

 

Output 

PNCST

  Provides a copy of the status information for the associated PROFINET Controller module. 

A_PSD

  Provides a copy of the Genius Communication Gateway status information from 

Bus A

B_PSD

  Provides a copy of the Genius Communication Gateway status information from 

Bus B

DSB_A

  Provides a copy of the device connection status for all Configured Genius devices on 

Bus A

DSB_B

  Provides a copy of the device connection status for all Configured Genius devices on 

Bus B

CSB:

 

Provides device connection status for all configured Genius devices on the dual bus pair. 

Содержание PACSystems* RX3i

Страница 1: ...n Controls For Public Disclosure Programmable Control Products PACSystems RX3i Genius Dual Bus Application Guide Application Guide GFK 2928 PACSystems RX3i Genius Dual Bus Application Guide GFK 2928 D...

Страница 2: ...no warranty as to the accuracy of the information included herein Changes modifications and or improvements to equipment and specifications are made periodically and these changes may or may not be re...

Страница 3: ...tomation com support Americas Phone 1 800 433 2682 International Americas Direct Dial 1 780 420 2010 if toll free 800 option is unavailable Customer Care Email digitalsupport ge com Primary language o...

Страница 4: ...System and Dual Bus References 8 3 3 Dual Bus Mapping Description 8 3 4 Development Environment 9 3 5 Simplified Description of Project Upgrade Steps 9 Chapter 4 Toolchest Components 11 4 1 Add Toolc...

Страница 5: ...Built in Ethernet Port of the CPU 24 5 4 Configure the PROFINET Controller Module 25 5 5 Configure the Genius Communication Gateway Modules 26 Settings Tab 26 GENIUS Gateway Parameter Tab 26 Genius D...

Страница 6: ...Paste INIT_GBnn Block 17 Figure 14 Rename and Edit INIT_GBnn Block 17 Figure 15 Genus Bus Number Assignment 18 Figure 16 PNC Assignments 18 Figure 17 GCG Assignments Bus A 19 Figure 18 GCG Assignment...

Страница 7: ......

Страница 8: ...ion solution Operates upon Dual Redundant Hot Standby RX3i PLC platforms Interfaces to existing Genius I O devices by way of PROFINET Controllers and Genius Communications Gateway modules Is scalable...

Страница 9: ...Chapter 1 Introduction 2 PACSystems RX3i Genius Dual Bus Application Guide GFK 2928 1 1 Revisions in this Manual Rev Date Description Dec 2017 Initial publication...

Страница 10: ...4 PACSystems RX3i PROFIBUS Modules User s Manual GFK 2301 PACSystems RX3i Max On Hot Standby Redundancy User s Manual GFK 2409 PACSystems RX3i Ethernet Network Interface Unit User s Manual GFK 2439 PA...

Страница 11: ...Genius Bus Switching Module CPE RX3i CPU with embedded Ethernet GCG Genius Communication Gateway GCG001 HHM Genius Hand Held Monitor MRP Ethernet Media Redundancy Protocol PME Proficy Machine Edition...

Страница 12: ...quired In the RX3i environment Genius devices must be interfaced via the Genius Communications Module GCG001 which then communicates over PROFINET with the host PLC GCG001 supports a number of differe...

Страница 13: ......

Страница 14: ...will require the following items to interface with each dual Genius I O network Four Genius Communications Gateway modules two associated with the Primary PLC interface and two with the Secondary PLC...

Страница 15: ...onfigured to have discrete inputs must have one block of references assigned to Bus A and a separate unique block of references assigned to Bus B The application logic is always solved using the refer...

Страница 16: ...Machine Edition Toolchest Edit the Primary Secondary Hardware Configurations Drag the Dual Bus application components from the Toolchest into the project s PLC Program Blocks Add Edit the Dual Bus Ap...

Страница 17: ......

Страница 18: ...d on the right side of PME Right click on the Toolchest to display a popup menu that will allow you to import a Toolchest Drawer Double click on the menu item Import Drawer Figure 6 Import Toolchest D...

Страница 19: ...items to your project While depressing the Ctrl key drag the following items from the Toolchest s DualBus folders into the PLC target Please make certain that the items are added in the proper order...

Страница 20: ...e as follows Group03 LDs Block Variable Name Entry INIT_GBnn no name required INIT_GB00 IGB00 ALM_DEV DEV EXE_CR CR01 Group04 LDs Block Variable Name Entry DB_SVCS DBS SW_BSM SW01 AUTO_SW Aut_Sw Group...

Страница 21: ...s perform the following INIT_GB00 This structured text block defines the parameters for a dual bus the instance is named IGB00 for Initialize Genius Bus 00 The block must be edited to match the specif...

Страница 22: ...his block will require editing in order to enter parameters that define the operation and devices on the corresponding dual bus Figure 10 Edit Genius Bus Definition Block s Note the variable on the le...

Страница 23: ...instance of the DBUS function block In this case the block refers to the first dual bus The name DB00 relates to the first bus Figure 11 Edit Block for Mapping Each Dual Bus Note the bus variable on t...

Страница 24: ...NIT_GBnn Block 3 Right click on Program Blocks in the Navigator pane The following pop up menu will be displayed Figure 13 Paste INIT_GBnn Block 4 Click on Paste Block 5 Because the block already exis...

Страница 25: ...st have a unique value that is in the range of 0 to 15 PNC Configuration Figure 16 PNC Assignments BUS PNC_SLOT2 The PNC slot number is used to identify the slot location in which the PROFINET control...

Страница 26: ...the Primary PLC Gateway module attached to Bus A BUS GCG_A GSDA The Genius Device Status bits for the Primary PLC Gateway module attached to Bus A Figure 18 GCG Assignments Bus B BUS GCG_B PRI_NUM The...

Страница 27: ...on Bus BUS Devices nn DI_Add This parameter applies to devices that contain discrete inputs It is the starting reference assignment for the device installed at Serial Bus Address nn BUS Devices nn DI_...

Страница 28: ...outputs must be configured so that the dual mapping routine can post loss of device or addition of device messages Also the device status i e the presence on either Bus A or Bus B is shared between th...

Страница 29: ......

Страница 30: ...Bulk Memory 65536 Symbolic Discrete 65536 Symbolic Non Discrete 65536 I O Discrete 65536 I O Non Discrete 65536 5 2 Transfer List Entries Input Transfer Points I configured for length 0 Q as needed M...

Страница 31: ...the Input Transfer List if you wish to perform automatic role switches based upon the loss of devices on a GCG Figure 21 Include ACTV_CSB in Input Transfer List 5 3 Configure the Built in Ethernet Por...

Страница 32: ...OFINET Status Address NOTE 1 For each slot in which a PROFINET Controller is installed the Primary module and the Secondary module will always have identical Status Addresses However the PROFINET Cont...

Страница 33: ...ty Genius Device Fault state and GCG Module OK Refer to the PACSystems RX3i Genius Communications Gateway User Manual GFK 2892 Section 5 1 1 Figure 26 GCG Gateway Status Data Reference Assignments NOT...

Страница 34: ...e G_Bus Note that the parameters are configured using the function blocks derived from either INIT_GB00 or INIT_GBnn Output PNCST Provides a copy of the status information for the associated PROFINET...

Страница 35: ...me View of Genius Devices on Dual Busses Device Status Bits Zoom into the block to observe the current connection status for all configured Genius devices on the dual bus pair Four rungs display the d...

Страница 36: ...to Bus A This reference may be turned on by selecting the contact and then right click The reference maintains its state NOTE The function will turn ON its fault output if TO_A and TO_B are both ON or...

Страница 37: ...LC and compare them with the Genius combined status bits in the Backup PLC The comparison is performed within the Serial Bus Address range of 01 29 If any bit in the Backup PLC is ON while it s compar...

Страница 38: ......

Страница 39: ...bers are available on our web site www geautomation com Additional Resources For more information please visit our web site www geautomation com Copyright 2017 General Electric Company All Rights Rese...

Отзывы: