5-122
N60 Network Stability and Synchrophasor Measurement System
GE Multilin
5.5 GROUPED ELEMENTS
5 SETTINGS
5
5.5.4 PHASE CURRENT
a) PHASE INSTANTANEOUS OVERCURRENT
(ANSI 50P)
PATH: SETTINGS
ÖØ
GROUPED ELEMENTS
Ö
SETTING GROUP 1(6)
Ö
PHASE CURRENT
Ö
PHASE IOC 1
The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The input current is the fundamental phasor magnitude.
Figure 5–51: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC
PHASE IOC1
PHASE IOC1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
PHASE IOC1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2
MESSAGE
PHASE IOC1
PICKUP: 1.000
pu
Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
PHASE IOC1 PICKUP
DELAY: 0.00
s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PHASE IOC1 RESET
DELAY: 0.00
s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PHASE IOC1 BLOCK A:
Off
Range: FlexLogic™ operand
MESSAGE
PHASE IOC1 BLOCK B:
Off
Range: FlexLogic™ operand
MESSAGE
PHASE IOC1 BLOCK C:
Off
Range: FlexLogic™ operand
MESSAGE
PHASE IOC1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
PHASE IOC1
EVENTS: Disabled
Range: Disabled, Enabled
IA
≥
PICKUP
SETTING
PHASE IOC1
FUNCTION:
Enabled = 1
Disabled = 0
SETTING
PHASE IOC1
SOURCE:
IA
IB
IC
PHASE IOC1
BLOCK-A:
Off = 0
SETTING
SETTING
IB
≥
PICKUP
RUN
PHASE IOC1
PICKUP:
RUN
IC
≥
PICKUP
RUN
PHASE IOC1
PICKUPDELAY:
SETTINGS
PHASE IOC1 RESET
DELAY:
t
PKP
t
RST
t
PKP
t
RST
t
PKP
t
RST
827033A6.VSD
FLEXLOGIC
OPERANDS
PHASE IOC1 B PKP
PHASE IOC1 B DPO
PHASE IOC1 PKP
PHASE IOC1 C PKP
PHASE IOC1 C DPO
PHASE IOC1 A OP
PHASE IOC1 B OP
PHASE IOC1 OP
OR
AND
OR
AND
AND
PHASE IOC1 A DPO
PHASE IOC1 A PKP
PHASE IOC1 C OP
PHASE IOC1
BLOCK-B:
Off = 0
SETTING
PHASE IOC1
BLOCK-C:
Off = 0
SETTING
PHASE IOC1 DPO
AND
Содержание N60 UR Series
Страница 2: ......
Страница 4: ......
Страница 330: ...6 24 N60 Network Stability and Synchrophasor Measurement System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 340: ...7 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 436: ...B 78 N60 Network Stability and Synchrophasor Measurement System GE Multilin B 4 MEMORY MAPPING APPENDIXB B ...
Страница 474: ...D 10 N60 Network Stability and Synchrophasor Measurement System GE Multilin D 1 IEC 60870 5 104 PROTOCOL APPENDIXD D ...
Страница 486: ...E 12 N60 Network Stability and Synchrophasor Measurement System GE Multilin E 2 DNP POINT LISTS APPENDIXE E ...