GEK-113032A
W650 Wind Generator Protection System
2-21
2 PRODUCT DESCRIPTION
2.4 TECHNICAL SPECIFICATIONS
2
2.4.6.6 IRIG-B INPUT
2.4.7 REAL TIME CLOCK
2.4.8 OUTPUTS
Amplitude modulation:
DC SHIFT = Demodulated input (no carrier)
Input Voltage:
TTL
Input Burden:
1.5 mA
Input Impedance:
3.3 kOhm
Minimum Input Voltage:
2.4 V
Maximum Input Voltage:
+/- 24 V
Formats:
B000 (*) B001, B002 and B003 (*)
(*) Signal combinations recognized in accordance with IRIG Standard 200-95
Isolation:
2 kV
Accuracy:
Typical
±
20 ppm
Backup energy:
More than 1 week
Carry continuous:
16 A
Make and Carry for 1 sec
60 A
Break at L/R of 40 ms:
0.3 A DC max. at 125 Vdc
0.25 A DC max. at 250 Vdc
Operate Time:
< 8 ms
Contact material:
Silver Alloy
Output Logic Type, Output Type and Pulse Output Time are selectable by setting for each output
Output Logic Type
Positive / Negative
Output Type
Normal / Pulse / Latch (Selectable by setting for each output)
Pulse Output Time
0 to 60000 ms in steps of 1 ms (applicable only to signals set as pulse type)
Separate operate and reset signal can be configured by any digital signal programmable through PLC
Contact Outputs (F31-F33, F34-
F36) for board type 2 (supervision)
in slot F:
The current seal-in circuit is used for verifying the current condition in a circuit
during the time that the tripping contact remains closed. If the current in the
tripping circuit is maintained over 100 mA, the function is sealed independently of
the status of the function that caused the trip.
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...