GEK-113032A
W650 Wind Generator Protection System
10-9
10 BOOTCODE AND FIRMWARE UPGRADE
10.3 FIRMWARE VERSION UPGRADE
10
10.3FIRMWARE VERSION UPGRADE
The relay settings and configuration will be lost, so it is advisable to save them to a file.
Take into account that if the
boot code has been previously upgraded, all the data (including calibration settings) was lost.
In case of error during the firmware upgrading process, the user could repeat the whole process as many times as
necessary, this is possible thanks to an independent boot memory (bootcode).
The firmware upgrading process should be done using the EnerVista 650 Setup software, after connecting the relay by
Ethernet port (COM3).
10.3.1 FIRMWARE UPGRADE
Once the communication with the relay through Ethernet connection has been verified
1
, enter the EnerVista 650 Setup
program, select
Communication
and the
Upgrade Firmware Version
option.
Therefore, it is necessary to save all settings to a file before following with the process
.
Figure 10–16: FIRMWARE-BOOT VERSION COMPATIBILITY
After accepting to proceed, a window will open up for the upgrade parameter.It is also necessary to enter the ordering code
for the relay. See figure below:
This change is due to the multilingual implementation in W650 devices. See ordering code section in product description
chapter in this manual (section
1. Calibration settings should be stored in a file before upgrading the firmware.
Go to EnerVista 650 Setup main menu “
Communication > Calibration > Get Calibration Settings
”
Store the file in the PC using the relay serial number, for instance, as the name of the file.
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...